ID Area Issue Action Date PIC
100 BOPP_1 ground panel showed ERR, found on-board CPU in reset. After restoring watched several missions, no issues see above 2024-08-12 14:23:26 Glenn Hasdorff
107 CFP wrapper would not run. got here 22:00 23:00 replace belt and shim for sensor on carriage. 2025-12-22 14:56:15 Joe Moya
148 BOPP_1 line 14 inside shuttle wouldn't move No alarms but missing safety OK light on PS1A stand. Inspected and cleaned off shuttle's obstacle sensors. 2022-07-22 05:40:34 JonVu
155 BOPP_2 Received call about stacker 1-3 not powering up. Checked stackers for power and checked the Warehouse PC for warehouse status. The program didn't have communication with any machine. Stackers were shown offline and missing communications with Entry, Exit, US, LS, and DB. Had to call Yiduo for help, and received a call for the BOPP1 JR shuttle. 2022-07-22 05:39:53 JonVu
156 BOPP_1 Received a call about a broken belt on the JR shuttle caused by the plastic debris. Inspected the JR. Found a broken encoder belt and called Alfredo for assistance on how to replace it. Once the belt was replaced, moved the shuttle and set the encoder value. Helped operation with mission issues and got production caught up. Follow-up on inspecting the shuttle, Lead reporting of JR shuttle not matching up to the floor mark on Line 3 and 4, and going into alarm on core pick-up. Made an attempt to readjust the encoder values. 2022-08-08 13:38:57 Benjamin Leita
157 BOPP_1 Line 14 inside tipper wouldn't change positions or allow cradle unload. Noticed that the sensors for the flappers (RB stopper) weren't on. Checked the panel and junction box for incoming voltage. Called Chase and he noticed the PX sensor was distanced too far from the flapper and tested sensors on both sides and it worked. Made adjustments and finished Sunday morning. 2022-07-25 15:20:06 JonVu
158 BOPP_1 Outside Tipper was stuck in position and wouldn't move. Found that the sensors that looked at the rotating shaft were all on. Replaced the broken sensors and did test runs to make adjustments. During the adjustment runs, I noticed the different sets of sensors were too far to read as well. The machine was shifting East-West and creating gaps for 1 set of sensors to read and breaking the other set of sensors. I was able to put the tipper in neutral for operations to pack out but had to disable cradle return and tipping to prevent further damage 2022-08-08 13:39:29 Toan Vu
161 BOPP_2 travel drive faults--'motor stalled' & 'RIO' revise X axis control and drive settings to eliminate stalling from conflict between two travel motors 2022-08-15 19:13:54 Paul Lopez
162 BOPP_2 travel drive faults--'motor stalled' & 'RIO' adjust or replace Leuze RIO light beam units to work reliably all the way to the north end of the warehouse and fix RIO errors 2022-08-15 19:11:38 Paul Lopez
163 BOPP_2 travel drive faults--'motor stalled' & 'RIO' reopen some warehouse locations that were disabled due to stalling 2022-08-01 19:38:15 Paul Lopez
164 BOPP_2 travel drive faults--'motor stalled' & 'RIO' feel temperatures of both X motors, should not be overheated now 2022-08-15 19:10:33 Paul Lopez
165 BOPP_2 travel drive faults--'motor stalled' & 'RIO' restore operation for both X motor brakes (one was bypassed by Ben previously due to the conflict between the motors) 2022-08-15 19:10:54 Paul Lopez
166 BOPP_2 travel drive faults--'motor stalled' & 'RIO' update drive panel print to show axis & encoder changes 2022-08-01 19:41:08 Paul Lopez
167 BOPP_2 travel drive faults--'motor stalled' & 'RIO' PLC program--restore X motor current alarms that were disabled previously 2022-08-01 19:41:23 Paul Lopez
169 BOPP_2 travel drive faults--'motor stalled' & 'RIO' revise X drive replacement procedure with offset adjustment added 2022-08-15 19:13:37 Paul Lopez
170 BOPP_2 case# 170 travel drive faults--'motor stalled' & 'RIO' case# 170 setup and test spare X drive bought from Ebay, keep ready on crane 2024-08-05 08:59:39 tyler garza
172 BOPP_2 travel drive faults--'motor stalled' & 'RIO' clean up spare Z drive on top of crane, wrap and box it to protect it 2023-02-14 19:36:57 Nicolas Solis
173 BOPP_2 travel drive faults--'motor stalled' & 'RIO' clean up wiring in drive panel where 24 Vdc power supply was replaced 2022-08-15 19:14:10 Paul Lopez
174 BOPP_2 travel drive faults--'motor stalled' & 'RIO' Fix or replace cable connector at east travel motor so it isn't hanging on the wires 2023-02-14 19:38:16 Nicolas Solis
175 BOPP_2 travel drive faults--'motor stalled' & 'RIO' check all connections tight at both breakers for X drives 2022-08-15 19:14:44 Paul Lopez
176 BOPP_2 travel drive faults--'motor stalled' & 'RIO' Make sure ComCap logging of Crane 4 faults is working reliably in utility PC (ongoing repairs of utility PC in progress) 2022-08-08 20:02:35 Glenn Hasdorff
177 BOPP_1 slitter down with PLC program fault, looked like network comm issue but was not Make Intermapper map for Chara that shows RDS connections to Geobel slitters with real time monitoring 2022-08-15 19:16:08 Paul Lopez
178 BOPP_1 east hoist motor encoder cable fell out replace failing brake inside east hoist motor causing vibration 2022-08-01 19:44:04 alfredo pinon
179 BOPP_1 east hoist motor encoder cable fell out correct broken encoder mounting inside east hoist motor 2022-08-01 19:52:15 alfredo pinon
180 BOPP_1 east hoist motor encoder cable fell out replace failing brake inside east hoist motor causing vibration 2022-08-01 19:44:23 alfredo pinon
181 BOPP_1 east hoist motor encoder cable fell out on-board panel, west door-transformer panel fell through floor 2022-08-08 13:41:04 chase stary
182 BOPP_1 east hoist motor encoder cable fell out Fix D cell memory battery on ground panel Easy power supply, memory battery message is showing on screen 2022-08-10 15:08:59 chase stary
183 BOPP_1 east hoist motor encoder cable fell out X travel drive plastic housing has completely fallen apart due to ozone deterioration, set up and install a replacement drive 2022-09-19 19:47:52 Paul Lopez
185 BOPP_1 east hoist motor encoder cable fell out Complete the silicone to hold the hook sensor cable in place, west hook (facing N) 2022-08-09 16:23:30 chase stary
186 BOPP_1 "intermittent shutdowns, white light off-- possible cause is disturbance on PLC network, so look for any PLC network issues " Install managed ethernet switches in P3 board and ground panels, requires some 24Vdc rewiring to fit single wire in terminals on new switch 2022-08-12 19:40:43 chase stary
187 BOPP_2 BP2 Crane 2 having frequent read/write errors, replace radios BP2 Crane 2 having frequent read/write errors, replace radios 2022-08-01 19:57:10 Nicolas Solis
188 BOPP_2 BP2 Crane 3 having frequent read/write errors, remove radios BP2 Crane 3 having frequent read/write errors, remove radios 2022-08-01 19:57:26 Thomas Learn
189 BOPP_2 Make sure ComCap logging of Crane 4 faults is working reliably in utility PC (ongoing repairs of utility PC in progress) Make sure ComCap logging of Crane 4 faults is working reliably in utility PC (ongoing repairs of utility PC in progress) 2022-08-08 20:03:08 Glenn Hasdorff
190 BOPP_1 Troubleshooting the recent Crane 4 drive fault and P3 possible comm issues depends on the Utility PC working right to record drive faults and PLC read/write errors Utility PC-Fix the bootup problem, requires replacing the network cards, parts on order 2022-08-08 20:03:47 Glenn Hasdorff
191 BOPP_2 Troubleshooting the recent Crane 4 drive fault and P3 possible comm issues depends on the Utility PC working right to record drive faults and PLC read/write errors Get SNMP and ping working in the utility PC after the Win10 reinstall 2022-08-01 19:58:03 Glenn Hasdorff
192 BOPP_2 Troubleshooting the recent Crane 4 drive fault and P3 possible comm issues depends on the Utility PC working right to record drive faults and PLC read/write errors Install ComCap version 5 upgrade 2022-08-08 20:04:02 Glenn Hasdorff
193 BOPP_2 Troubleshooting the recent Crane 4 drive fault and P3 possible comm issues depends on the Utility PC working right to record drive faults and PLC read/write errors Change to SSD drive, keep capture files in hard drive 2022-08-08 20:04:26 Glenn Hasdorff
194 BOPP_2 Troubleshooting the recent Crane 4 drive fault and P3 possible comm issues depends on the Utility PC working right to record drive faults and PLC read/write errors Reinstall all the needed programs in the utility PC after previous hard drive crash 2022-08-01 19:59:21 Glenn Hasdorff
195 BOPP_1 Followup items to complete the RDS & slitting handling network installation Line 14 operator desk--connect permanent power for PC34, cables are in place 2022-12-15 14:23:22 Paul Lopez
196 BOPP_1 Followup items to complete the RDS & slitting handling network installation Roof of MCC room--reseal two 2" conduits down to network cabinet to stop water leaking into the PC/network cabinet below 2022-08-09 15:21:39 chase stary
198 BOPP_1 Followup items to complete the RDS & slitting handling network installation Network cabinet--Label KVM after water leak fixed and mildew cleaned up 2025-12-19 14:31:10 Glenn Hasdorff
199 BOPP_1 Followup items to complete the RDS & slitting handling network installation PC8 cabinet--connect direct to Digi instead of through 5 port sw 2022-08-01 19:56:28 Glenn Hasdorff
200 BOPP_1 Followup items to complete the RDS & slitting handling network installation MCC room--mount and connect the access point outside office 2022-08-26 18:39:04 Nicolas Solis
201 BOPP_1 Followup items to complete the RDS & slitting handling network installation Network cabinet--cover all openings in the top of the new network cabinet to keep dust from falling in 2024-07-25 13:42:21 Nicolas Solis
203 BOPP_1 Followup items to complete the RDS & slitting handling network installation Line 13 PC5 cabinet--install network jacks, fix wiring 2022-08-01 20:01:05 Thomas Learn
204 BOPP_1 Followup items to complete the RDS & slitting handling network installation MCC room--completely remove old network cabinet on wall and associated conduit 2022-08-09 15:22:24 chase stary
205 BOPP_1 Followup items to complete the RDS & slitting handling network installation MCC room--clean up the last of the installation stuff 2022-08-09 15:23:07 chase stary
206 Others Followup items to complete the RDS & slitting handling network installation Glenn's cart--find new home for all items to empty the cart 2024-08-12 14:23:45 Glenn Hasdorff
207 BOPP_1 Followup items to complete the RDS & slitting handling network installation.. MCC room--install a Digi IA (not IAP) inside the Goebel 11 panel, connect to network, make serial cable to connect to S5 PLC cancelled 2024-08-12 14:25:52 Glenn Hasdorff
208 BOPP_1 Followup items to complete the RDS & slitting handling network installation P2 crane on-board and ground panels--install the managed switches which were temporarily used in Line 14, requires some 24 Vdc rewiring to fit single wire in terminals on new switch 2022-08-10 15:08:25 chase stary
210 BOPP_1 line 14 outside tipper stopped in half tilt could get the ok light so that pointed me to a E stop pushed found one pushed on tipper from were they stack up the end boreds 2022-07-29 23:33:19 chasestary
212 BOPP_1 Call in line 14, reel handling shuttle not working. Found two E-stops push in at operator station. reset E-stops 2022-08-03 19:17:59 benjaminleita
213 CFP Call in conveyor table 50 would not run. Found no 24 volts to stop button. Trace power source back to height sensor. Replace sensor. also found that over load relay not working, replace relay. 2022-08-08 13:48:30 benjaminleita
214 BOPP_2 original flappers have been repaired Seval times need to be replaced and upgraded Replacing all open and close flappers on packing cranes 21,22,23,24&25 2023-03-29 19:30:23 Nicolas Solis
215 BOPP_2 drive motor needs to be replaced at 96 dispenser motor need to ordered install and test 2022-12-19 20:28:54 Paul Lopez
216 BOPP_1 heating wire broke in half on the wrapper came in removed broken heating wire on the wrapper found some more in bopp1 office replaced and adjusted tension watched a couple runs and went home. 2022-08-12 12:50:02 Nasalapicus
217 BOPP_2 stacker 3 jumped in value for X travel encoder was not in the right position came in trouble shot the issue found encoder arm had some slack in it tightened up arm and checked tracker for debri found nothing got stacker into right position and entered right value watched a few missions and left. 2022-08-15 12:41:07 Nasalapicus
218 BOPP_2 Operators ran into one of the sensors for the crosswalk with a fork lift was giving emergency E-stop alarms and not allowing JR shuttle to move i came in replaced broken sensor aligned it correctly and reset all alarms homed out shuttle and cranes watched some missions finish before leaving 2022-08-15 12:49:31 Nasalapicus
223 BOPP_2 PDU1 in the east JR control room Rack01 failed after a shutdown and was temporarily replaced with a plug strip Configure and install replacement PDU 2022-12-19 20:31:39 Glenn Hasdorff
226 BOPP_1 packing crane blow north and south fusses replaced fusses but need to see why fusses blow 2022-09-19 19:48:50 Paul Lopez
227 BOPP_1 would not power up found start button broken. got it back together and powered up but start button need to be replaced 2022-09-19 19:49:02 Paul Lopez
228 BOPP_1 bad sensor on outside cart. also, org packing crane 12 had no remote. upgrade sensor and have ready to go spares in bp1 shop.. 2022-09-19 19:48:04 Paul Lopez
229 BOPP_2 line 15 no communication err err err PLC showing fault had to call for help. Bad card in slot 7 2022-09-15 13:41:54 joe
230 CFP CFP Stacker 1 communication not working. Network connection was good, but heartbeat was not working. Found CPU in stopped state. Alarms indicated a safety shutdown related to Z and Y drive. Found Drive Cliq cables with tabs broken off and the connector loose and dirty. Cleaned and re-secured connectors. Cleared alarms and restarted - working ok. Follow up: Replace the connectors on the Drive Cliq cables or replace the cables as needed. 2024-07-19 13:55:31 Thomas Learn
231 BOPP_1 metalizer packing crane went down would open or close or go north only could go up, down and south got there around 6:25pm left at 7:20pm i troubleshot the machine checked the limit switches and rotary switches with the help of ben and chase from the phone we found it to be the remote on the packing crane took the one from a packing crane that could be down and swapped them and ran good 2022-10-27 12:43:13 chase stary
232 BOPP_2 crane 4 tripped CB5 120 volt breaker and would not run in auto would trip every time crane would make a move troubleshot the issue for awhile and had to call thomas to help, we found out the issue was with the AC, we bypassed the breaker so they can run and get their rolls out, although will need to make a follow up . 2023-02-14 19:40:43
233 BOPP_1 operator said monitor shut off and wouldnt turn back on troubleshot issue changed out the monitor worked fine until operator tried to run machine with the help of glenn i troubleshot the issue found the problem with the ez power supply on the chassis fixed the adjustment to 5.5 was at 5.3 restarted machine and watched a couple missions ran fine. 2022-10-01 07:21:13 Nicolas
234 BOPP_1 ergon 13 had same issue as the night prior this time. this time decided to change out the power supply and make sure it was adjusted correctly watched it run for awhile looked good. 2022-10-27 12:42:15 chase stary
238 BOPP_1 ergon 13 losing power found high voltage on power supply so pulled it and went to pauls office and tested some and found a couple bad ones so adjusted the orginal one and put it back in 2022-10-05 00:44:13 chase
239 BOPP_2 oprator hit sensor pole at cross walk found the pole bent so bent it back and aligned sensors 2023-02-14 19:40:50
240 CFP table wont go down and ergon losing power got a call that table wont go down came in and found that table was at the full height and at its emergacny limit after looking around a while found that the coil on the pump motor the wires were ripped out of it and so after looking around for a little while i couldnt find a pre wired 24volt coil so the lead told me to leave it down for the night then as i was headed to clock out about 2 bopp1 called and said that ergon 13 was losing power randomly so checked voltage it looked good saw two runs come out all looked good then as i was wrapping up it lost power so checked voltage again it was low so i got a new power supply and stay to monitor it for a while everything is still running good 2022-10-07 15:20:49 chase
241 BOPP_1 3 pallet crashes back to back they had 3 pallet crashes back to back on td 2 so came in and looked didnt see any sensors messed up so restarted the warehouse program and watched 10 pallets come to td 2 and all ran good only 60 cells left told ray if he starts havng problems back to back dont call disable entry to 2 and put all up in 3 since they have 200 open cells. follow up need to look into td and stacker 2 program to see if there is any changes from the other tds and stackers 2022-10-27 12:43:32 chase stary
242 BOPP_1 had two call ins during this time first was the wrapper in BOPP1 a pallet had some plastic hanging off caught one of the yellow sensors and unaligned it the operator tried to fix the issue but moved other sensors and got more unaligned. troubleshot the issue then proceeded to realign all sensors watched them run a couple missions 2022-10-10 12:35:59 Nicolas
243 BOPP_1 this is the second call in stacker 1 and transfer deck one both lost power completely and wouldnt power on at all i troubleshoot the issue inspected in the panel and the busbar noticed 3 cables on the stackers current collectors had fallen out i made sure to turn off power completely and isolate the machine before working on it wired the cables back up made sure they were tight started everything up and watched them send pallets from entry before leaving for the night 2022-10-10 12:40:13 Nicolas
248 BOPP_2 lower shuttle started ran away everytime it tried to make a move and moved frantically came in troubleshot issue couldn't find it out so i called ben he came out to help we spent some time troubleshooting went through a bunch of different problems and we found out the encoder coupling was broken changed it out on shuttle, while we were here we had to work on the panel view on entry had to have thomas come in and help me and ben change out the screen and reloaded the program on memory card 2022-10-10 15:35:07 Nicolas
249 BOPP_1 broken chain on TD1 replace chain and adjust 2022-10-11 00:26:52 chase
250 BOPP_1 thermal relay trip on hydo pump came in and found it tripped so ran it in manual and the pump was lugging like it was sucking air so added hydralic oil to it and it was doing the same so checked my power out the breaker and good there then checked at the contactors it was good there so put my amp clamp on each fase to see it the motor was over ramping didnt have anything on one leg so killed power and came back to the contactor and ohmd across and found i had a bad contactor so replaced with the upgraded model and then cleared all pallets that were lost on it and its in auto running good 2022-10-11 08:40:01 chase
251 BOPP_1 packing crane wont go north or south or up or down found two tripped breakers on packing crane 12 reset and running good 2022-10-16 07:25:58 chase
252 BOPP_1 packing crane 12 not going north or south found tripped breaker reset and running 2022-10-17 02:37:43 chase
258 BOPP_2 X 1 drive fault case # 258 x 1 drive was showing no 24v. found blown fuse in drive (f2) also loss wire (number 10). after replacing the fuse, we were getting a RT fault that was caused by the loss number 10 wire. follow up: encoder wiring diagram needs to be clear. 2024-06-05 08:13:23 tyler garza
259 BOPP II X 1 drive fault x 1 drive was showing no 24v. found blown fuse in drive (f2) also loss wire (number 10). after replacing the fuse, we were getting a RT fault that was caused by the loss number 10 wire. follow up: encoder wiring diagram needs to be clear. 2022-12-14 21:05:39
261 BOPP I packing crane 12 tripped, and when i left halfway home i got called in again about packing crane 14 driving slow north and south came in reset breaker on packing crane 12 watched it run for a bit ran well and left, while on way home got another call about packing crane 14 moving slow troubleshot the issue but could not find the issue they said they could leave it down for the night and use the other crane. 2022-11-29 20:44:21 Glenn Hasdorff
269 BOPP_1 Ground panel showed ERRs and on-board EASY CPU in reset. 1 Checked EASY power supply and connections - all good. 2 Re-seated all boards in EASY chassis and test - still in reset. 3 Moved CPU and ram disk boards to different slot in chassis - still in reset. 4 Replaced CPU and ram disk with spare (known bad) powered up ok, but goes into reset at startup 5 Re-installed original CPU/RD set in original slots and removed all other cards - powered up OK 6 Re-installed I/O card and AXIS cards one at a time and test - always powered up OK 7 Cycled power to Crane and Ground panel and started up normally - Observed several missions before leaving 2022-12-09 13:35:10 Thomas
270 CFP wrapper clamp broke bolts on gear came in replaced bolts and put gear back together 2022-12-12 13:40:55 Nicolas
271 CFP chain on roller table broke the master link due to a piece of wood getting jammed inside the chain and gear removed broken piece of wood and got a new master link installed chain tightened gear watched a couple runs it ran well 2022-12-12 13:42:23 Nicolas
275 CFP bolts backed out of pillow block bearings need to maybe put maybe lock nuts are a drip of lock tight on bolts 2023-05-08 16:37:31 Admin Ash
276 CFP Got a call at 6 am this morning cfp had a broken chain on conveyer going to stacker 1 let joe know already this morning joe working on it this morning 2022-12-16 13:50:46 Doro
277 Support all warehouse programs need updated and achieved into our data server for easy download Update and transfer files 2023-05-27 02:10:49 Yiduo Wang
278 Support parts ordering from each individual is not standard. It is not easy for parts coordinator to process the paperwork due to incomplete info. create an easy ASH entry to let everyone easy ordering parts he needs. 2022-12-20 02:40:38 Yiduo Wang
280 Support the good work from everyone is not properly storage so we often need to look back when tunning in the improvement initiatives. Create a paper sorted by username so anyone can easily see all the good work (improvement) he has done 2022-12-20 02:40:24 Yiduo Wang
283 CFP Friday night 12-16-22 got called bay 123 would not transfer pallets to the up and down bay so stacker could not pick up chano moved the pallet to the next table that the pallet showed then moved the information to the table and into automatically picked up udc and clear table 2022-12-19 14:36:42 Doro
284 BOPP_2 Saturday 12-17-22 stuck flapper on open and close packing crane 21 just modify flapper arm by grinding down the inside flapper 2022-12-19 14:39:07 Doro
294 BOPP_1 operator called around 21:30 said shuttle will not move 1. check power 2. check fuses 3. check power at shuttle. no power to shuttle 4. after turning power back on i tried to move shuttle and it worked. i was able to move shuttle back and forward about 10 times then it stopped again. reset panel then it worked again. operator had about 5 rolls to move around so i told him if it stops again just reset panel. follow up: shuttle is still shutting off 2023-03-30 18:28:23
299 CFP Exit table sensor condition not clear. stacker not delivering the pallet for unknow reason Study the exit bay "ready" condition for stacker to deliver the pallet. Make a sensor page to assist if necessary 2023-05-31 23:29:04
304 Support need a working procedure to trouble shooting OPC related issues create a PDF help file 2024-08-06 15:06:03 Yiduo Wang
305 BOPP_1 When data transfer after doffing not work due to operator keyed in wrong width, the system stuck create a function to allow operator to modify the setup data to match the actual machine to allow data match and transfer. the abnormal will be logged for mangement review. 2024-04-23 09:27:32 Yiduo Wang
306 CFP pre-stretch chain and belt came off. loose nut. added lock washer to tension pully. 2023-01-03 19:48:00 Benjamin Leita
307 CFP folks sensor block broke off. fab and installed new block 2023-01-03 19:51:42 Benjamin Leita
308 CFP folks sensor block broke off. fab and installed new block 2023-01-03 19:52:06 Benjamin Leita
309 BOPP_2 at 6pm had a pallet crash at the top of the cells it was a twisted pallet with small 48 stack of pallets on board came in made sure to get my safety equipment and harness on went up straightened out pallet pulled it out of the cell into stacker unloaded stacker and realigned blue sensors 2023-02-08 17:16:31 Nicolas Solis
314 CFP operator report a busted veldt on rotating arm found a new veldt on the room inside warehouse and proceed the installation 2023-01-09 14:27:20 Alfredo Pinon
315 CFP operator report a busted veldt on rotating arm found a new veldt on the room inside warehouse and proceed the installation 2023-01-09 14:27:23 Alfredo Pinon
317 BOPP_2 flipped pallet on upper transfer deck 1 recovered pallet had to take down manually check sensors and hand check 2023-01-13 01:33:24 Doro Villegas
318 CFP broken chain on drive motor check out sprocket for wear replaced chain and master link adjusted chain tested. 2023-01-13 11:56:53 Doro Villegas
319 CFP 1-14-23 broken ideal rollers. easy out broken bolts lock tight new bolts, tested 2023-01-16 13:43:24 Doro Villegas
320 BOPP_2 Broken LB for wire charger station in warehouse Work Order # YD10BRE Cost Center 6A81 Remove and replace broken LB. 2023-02-14 19:37:12 Nicolas Solis
321 BOPP_2 SHIPPING TABLE B SCISSOR TABLE WILL NOT GO UP OR DOWN REPLACE SISSOR 2023-03-29 19:30:43 Alfredo Pinon
322 BOPP_2 operator report that sprocket fail from the rotating arm i found the bolt that holds the sprocket has Brocken that's way the sprocket fail that sprocket goes on the out put shaft from the gear box i drill the broken bolt left on the gear box side and install sprocket with new bolt and getting wrapper running again on automatic not need a follow up on it 2023-02-06 13:42:56 Alfredo Pinon
323 BOPP_1 heat treated wire broke to cut film. installed and replace wire with new wire. And tested. 2023-02-08 02:30:04 Doro Villegas
325 BOPP_2 bad motor need to replace bad motor on 96 exit system. And find out why it keeps burning up motors. 2023-07-06 23:50:33 Nicolas Solis
326 BOPP_2 old and bad air hose need to replace air hose on packing crane. 21-24 2023-03-29 19:30:59 Alfredo Pinon
327 BOPP_2 cross over at pallet island cover tables add grading to cover table and build 2 steps to get from one side to the other. Safely 2023-03-29 19:31:09 Alfredo Pinon
328 BOPP_1 broken conveyor chain ( far east side ) repaired chain 2024-08-05 09:13:59 Joe Villarreal
329 BOPP_2 broken LB needs to be replaced. shut down power disconnect wires take old LB off install new Lb reconnect wires. 2023-02-14 19:37:18 Nicolas Solis
330 BOPP_2 Call in crane 4, making loud noise Found 4 bad up/down guide bearing west side. replace bearing. 2023-02-14 17:02:52 Benjamin Leita
332 BOPP_1 P2 would not power up had ERR on ground panel 1. Went up crane opened panel doors check to see if easy was on no power. 2. Looked around found that a breaker was tripped so reset then saw some smoke .3.Turned off breaker. 4. moved what look like a small capacitor and reset breaker. it stay on and P2 ran some missions. 5. check into capacitor replacement. 2023-03-30 18:26:50 Chase Stary
333 BOPP_1 Got a call last night around 9 that P2 would not power up and that ground panel had ERR on the screen . Came in went up to onboard panel opened doors saw that easy was not on looked around found tripped breaker so reset then I saw smoke coming from a small capacitor turned breaker off. Separated capacitor from wire. Then I reset breaker and it stayed on so had Javier power up crane put in auto. Watched it run some missions. Left around 10:50 Follow up: Check on capacitor replacement. We are looking into it got Thomas the wire numbers this morning the capacitor that is burnt goes to a filter but there two filters wired in series we’re gonna get with Glenn to see if we need both filters if not we will just end up removing or replacing it 2023-03-30 18:27:29 Admin Ash
334 BOPP_1 We are looking into it got Thomas the wire numbers this morning the capacitor that is burnt goes to a filter but there two filters wired in series we’re gonna get with Glenn to see if we need both filters if not we will just end up removing or replacing it We are looking into it got Thomas the wire numbers this morning the capacitor that is burnt goes to a filter but there two filters wired in series we’re gonna get with Glenn to see if we need both filters if not we will just end up removing or replacing it 2023-03-30 18:27:19
335 BOPP_1 Crane would not power up pane view had ERR on it 1. Went up crane opened panel doors check to see if easy was on no power. 2. Looked around found that a breaker was tripped so reset then saw some smoke .3.Turned off breaker. 4. moved what look like a small capacitor and reset breaker. it stay on and P2 ran some missions. 5. check into capacitor replacement. 2023-03-30 18:27:25 Admin Ash
338 BOPP_2 Packing crane 22 vertical lift would not move in up slow speed and would actually drop lower and not be held by the brake Me and Thomas found the speed adjustments in the panel were turned past the limit so it was actually going backwards we adjusted the limit to the correct speed and it returned to its normal settings would run correctly. 2023-03-29 19:30:11 Nicolas Solis
339 BOPP_1 cross travel would not move north or south found a breaker trip 1103016fb on board panel... up and running 2023-04-01 12:09:30 Doro Villegas
340 BOPP_1 cross travel would not move north or south found a breaker trip 1103016fb on board panel... up and running 2023-04-01 12:10:42 Doro Villegas
341 BOPP_1 cross travel would not move north or south found a breaker trip 1103016fb on board panel... up and running 2023-04-01 12:18:27 Doro Villegas
343 CFP got called in around 1:30pm to 2:44pm april 8th the conveyor in CFP had a missing chain that would cause a section of rollers to not turn and cause the pallet to become crooked and become stuck came in found the spot that was missing chain went and got some new chain and installed that section watched run and it went good 2023-04-10 12:45:17
344 CFP got called in around 1:30pm to 2:44pm the conveyor in CFP had a missing chain that would cause a section of rollers to not turn and cause the pallet to become crooked and become stuck came in found the spot that was missing chain went and got some new chain and installed that section watched run and it went good 2023-04-10 12:40:57 Nicolas Solis
345 CFP 2:44am 3:54am april 9th conveyors in cfp lost power randomly came in found some loose wires in the panel tightened them and watched run didnt have any issue after that 2023-04-10 12:48:56 Nicolas Solis
346 BOPP_2 Fork gears broke on Stacker 3 we brought the forks down and pushed them out onto the transfer deck to remove the gears and replace them with brand new gears and shafts 2023-07-06 23:50:41 Nicolas Solis
347 BOPP_2 Stacker forks were all the way into the cell the gears and shafts on the forks busted and caused the forks to become stuck and would not move in or out we brought the forks down and pushed them out onto the transfer deck to remove the gears and replace them with brand new gears and shafts 2023-04-20 12:49:54 Nicolas Solis
348 CFP open close cramp would not work found broken air fitting and replaced 2023-04-21 05:18:35 Doro Villegas
349 CFP had 2 issues1st cradle on wrapper would not go up, wrapper hit a pallet that went too far and damage lower limit switch. the 2nd issue after it was running the cradle got stuck in the middle and would not go up or down would give a f005 fault on power flex 1st issue got limit switch fixed and adjusted. And got to worked. 2nd issue checks all signals on sensor and limits. check all wiring in panel and limits and sensors. change out power flex and reentered settings. clean &changes rotation arms brushes found bad rotation motor. 2023-04-24 13:02:51 Doro Villegas
350 CFP had 2 issues1st cradle on wrapper would not go up, wrapper hit a pallet that went too far and damage lower limit switch. the 2nd issue after it was running the cradle got stuck in the middle and would not go up or down would give a f005 fault on power flex 1st issue got limit switch fixed and adjusted. And got to worked. 2nd issue checks all signals on sensor and limits. check all wiring in panel and limits and sensors. change out power flex and reentered settings. clean &changes rotation arms brushes found bad rotation motor. 2023-04-24 13:02:58 Doro Villegas
352 BOPP_1 alfredo pinon ; operator call saying that crane was making noises during ex travel re locate the bad bearing on the west side of crane and replaced for the new one from 6;20 to 7;45 05/11/23 2023-05-11 12:54:01 Alfredo Pinon
354 BOPP_1 Chain on Upper Shuttle conveyor broke came in at 4:18am gathered all the tools and new chain then replaced the old chain i finished at 6:23am 2023-06-01 16:45:41 Nicolas Solis
355 BOPP_1 had some wood break off a pallet on the shuttle fall into the track upper shuttle ran it over and some fell into the encoder track operator did not clean it and the caused the shuttle to bind and push the belt on encoder off i came in at 1:16 am cleaned up left over wood and loosened the encoder belt and put it back together tightened the belt back to original adjustment and watched a couple runs before heading home left at 2:17 am 6/3/2023 2023-06-05 22:54:54 Nicolas Solis
356 CFP Pallet would move on to table 40 after scanner After troubleshooting found inverter fault F13 which is ground fault (Check motor and external wiring for a grounded condition. Found that the flex from motor to panel had been smashed exposing wire which was touching the metal flex. 2024-08-12 14:25:04 Glenn Hasdorff
358 BOPP_1 I was call in at 17:30, To run P-2 to help get J/R off line 14. They call to cancel call in. 2023-06-21 16:37:07 Benjamin Leita
359 BOPP_1 Call in on conveyor table, but I didn't hear the phone at 21:30. I got a message at 04:00 called plant back but no answer, came in at 05:30 to fix, but Alfredo already fixed it. Teflon broke loose. Drill hole in Teflon and replace screws. Thanks Alfredo for fixing it. 2023-06-21 16:53:19 Benjamin Leita
360 BOPP_1 missions messed up and gave wrong location and the operator who knew how to fix it left so they needed someone to come in to get it all reset i came in went through the reset procedure with the help of chase got it all back into the proper locations had them clear missions and restart it watched it do a couple of runs and went home got there around 4:20 am left around 4:53 am 2023-06-26 17:32:00 Nicolas Solis
361 BOPP_2 crane 4 would not run any mission showing it was in shuttle area found broken rotary switch arm broke. 2023-06-29 12:25:06 Doro villegas
362 BOPP_1 broken chain on 1st entry table master link was broken replaced chain new master link 2023-07-02 03:32:13 Doro villegas
365 BOPP_2 the gear box for the forks leak all the gear fluid need to order a new replacement for it doing p-m on stacker #2 found forks gearbox has oil leak 2023-07-13 19:32:23 Alfredo Pinon
366 BOPP_2 wouldn't move north or south. trip breaker in panel 2023-07-23 14:31:41 Doro villegas
368 BOPP_1 CASE#368 broken outside cable carrier. CASE#368assembled what cable carrier that was left. yes, need to add extra cable back to cable carrier and mount correctly. 2024-06-05 08:13:54 tyler garza
369 BOPP_2 case# 369 crane 4 shutdown over jumbo roll shuttle, and would not start back up, could not get run gml was showing a estop pushed. could not find estop pushed. so, we had to jump the estop on board and replace a number 3. fuss case# 369 need to replace old wiring from brushed to Junkin box. Asap 2024-08-05 08:59:24 tyler garza
370 BOPP_1 operator report packing crane # 13 the open and close don't work need follow up on replace the contactors 2024-08-05 13:46:26 Benjamin Leita
371 BOPP_1 CASE#371 the shuttle has a missing and Brocken Estops CASE# 371 shuttle don move estops been push and Brocken sometimes hard to recover 2024-08-26 14:16:19 tyler garza
372 BOPP_1 CASE# 372 packing crane 13 remote control need a replacement CASE# 372 Brocken limit switch on open and close clamps/ fixed 2024-07-19 08:45:10 Eric licerio
374 BOPP_1 Got called last night for bopp1 transfer deck 3 would not power up or move isles just rebooted and found top pin sensor not making correct mad a adjustment tested could not delete stuck mission .Yiduo deleted it got back in service and running Thanks Doro V WATCH PIN COME UP BUT SENSOR WOULD NOT MAKE 2023-12-05 07:43:13 Doro villegas
375 BOPP_1 CASE# 375 cutter arm wire broke CASE# 375 would not cut plastic, follow up need to order or find roll of cutting wire. replaced old wire issue completed 2024-08-12 09:31:50 Eric licerio
376 CFP pallets would not wrap or pallets would not stop entering wrap machine. system was out of sequence. middle blue sensor needed ajusting had to clean everything off table and restart system. 2023-12-12 06:39:21 Doro villegas
377 BOPP_2 lost communication would not go east past cross walk some hit cross walk sensors bracket was completely dead had to religh all sensors. 2023-12-13 07:37:07 Doro villegas
379 BOPP_1 call in 0845 pm Current collector came out of busbar. fix 2024-01-16 12:53:54 Benjamin Leita
380 BOPP_1 It would die while traveling, sometimes due to motion faults while traveling slow, sometimes with inverter faults (‘shear pin’ fault from high current) when trying to travel fast. After lengthy troubleshooting, we happened to check the offset adjustment between the Easy and the drive and it was off. After doing the procedure to adjust the offset voltage then the crane would run correctly at 100% speed. Along the way we had lowered the acceleration rate so we will restore that adjustment tomorrow. 2025-12-19 14:29:22
381 BOPP_2 case# 381 call in packing crane 22 and 21 not working. case# 381 bus bar was separated. fix. 2024-05-07 08:11:46
382 BOPP_1 easy panel would not respond to program. changed easy & video card still got issues responding to program. 2025-12-19 14:30:45
383 BOPP_1 The main issue turned out to be that the position value for Line 4 was lost, as if the memory was corrupted. The position value for Line 4 should be 119915. As you can see in this screen shot from the CMA-B screen, it was a small negative number, -14.636, which is outside the allowable range. So any attempt to move to Line 4 caused a motion fault due to the illegal destination target. 2024-08-02 08:54:19
385 BOPP_1 JR shuttle would stop cycle getting to cross walk and by between lines 1 and 2 Trouble shoot what I thought was causing issue still was not moving after talking to Glenn he told me to check if CPU went into reset and it was, so I reseated the axis board and changed the power supply because the previous one when I pulled it out to check voltage it touched the chassis frame it blew fuse so I just put new power supply and fuse and still would go into reset next I walk away from shuttle to clear mind when I come back power still on I tap on easy chassis and it went straight to reset found issue chassis not stable next I tight all chassis frame screws around the chassis powered back up talk to Rosevelt to put in auto and run mission by then Glenn was arriving and it ran to line 4 and back to warehouse with out shutting off caught lines up seemed ok but for how long is the question. Follow up needed to replace chassis and make sure all guides are in place also to keep board from moving around so much. 2025-12-19 14:30:20
386 BOPP_2 case# 386 line 6 positioning sensor bracket broken. case# 386 weld bracket back on. Could not see what caused bracket to break off. follow up: 1. check sensor height. 2. check east emergency limit height 2024-05-07 14:56:47 eric licerio
387 BOPP_1 Crane waiting on shuttle. The P1 crane at Line 2 is now running shuttle missions in automatic and the line is restocked with cores. When Line 2 was restarted after a long shutdown period, the P4 crane at Line 2 would run the winder roll change missions in automatic but would not run the shuttle missions in automatic. When the shuttle arrived at Line 2, the crane did not move and the screen said “waiting on shuttle”. Operations chose not to use the backup shuttle to keep the line running. When Joe and I came in we found that the 24 volt interlock signals from the shuttle ground panel to the Line 2 crane panel were being correctly received by the crane so that was not the problem. After some checking we found that the serial communication between the Line 2 crane panel and the shuttle ground panel had completely quit working. There were two causes: 1. The 12 volt DC supply for the current loop communications had failed, the light for that supply was flickering. 2. The serial configuration for channel 2 in the crane had gone back to the default setting of 1200 baud. After replacing the current loop power supply and setting the channel 2 configuration back to 4800 baud the serial communication was restored, and the crane ran the shuttle missions in automatic. follow up: repair power supply. 2025-12-19 14:29:59 Paul Lopez
388 BOPP_1 operator said nothing would go in because she could not delete mission. also, stk2 showed pallet on platform but no pallet. 1st. call was at shift change so when i got here night shift operator deleted mission. 2nd. found pallet present sensor was not aligned because of damaged unistrut. I added washer so I can tighten sensor bracket. follow up: 1st training for operator. 2nd replace unistrut 2025-12-19 14:31:53 alfredo pinon
389 BOPP_1 CASE# 389 south cart cable carrier and cable damaged. CASE# 389 About 4ft peace was removed from the center of the cable carrier when I got there. I was able to reuse most of the cable carrier that was there. I had to butt splice one wire and tape another because it was bare. cable was for the chains on cart. follow up: spare parts. had a hard time locating parts. cable will have to be replaced because of butt splice. 2024-08-05 08:59:15 tyler garza
392 CFP pallet crash. entry stk3 pallet had missing slate causing pallet to twist and damage two sensors. remounted one sensor and replaced another. 2024-08-05 09:13:39 Joe Villarreal
393 BOPP_1 broken brushes on east assembly top and ground replace brush arms 2024-08-05 09:13:07 Joe Villarreal
421 BOPP_1 Panel PO-AW1 by the pallet warehouse has a missing breaker with cardboard in the hole. Replace the missing breaker to fill the hole. This requires a short warehouse shutdown to lock out the panel and remove the front cover. 2025-12-19 14:32:23
422 BOPP_1 Bonfanti PC is not integrated with RDS PC work with Bonfanti to move the functionalities into RDS client. After consulted with Bonfanti engineer, this function is not necessary 2025-12-15 15:34:48 Yiduo Wang
434 BOPP_2 case# 434 shuttle was randomly going into alarm, not moving, shutting down, Not stopping in-home position. case# 434 1.changed out sensor bracket wheel & sensors 2.changed out west side drive assembly 3.changed out northwest out rigger 4.change out chopper 5 recharged battery's and did a battery swap. 6.ajusted shuttle safety sensors 7 took best battery from bopp1 had and swap with bopp2. 8. found a wire loose from chopper had to re solder. 9.ben & glen found 2 bad contacts and jumped ,(replaced both bad contacts) 2024-05-22 13:46:49 tyler garza
444 CFP Several blue steel bent at north cells. Fix or remove the damaged steels. 2024-10-02 07:47:10 Joe Moya
445 CFP Some panel doors cannot be closed repair the door 2024-06-13 07:56:10 Not Assigned
446 CFP A junk pallet in a cell at north site remove the pallet 2024-06-13 07:56:19 Not Assigned
449 BOPP_2 RDS system upgrade to work with Goebel HMI Ash and RDS programming 2025-11-25 11:59:00 Yiduo Wang
451 BOPP_1 inside shuttle would not move in auto or manual notice red light on laser check out problem, rebooted, check fault in panel check all estops and sensors, checked safety bumpers, took laser off shuttle took apart and clean glass and eye inside laser, started running after we clean and wipe down glass from laser follow up add to pm checklist 2025-12-19 14:32:39 Doro villegas
452 BOPP_1 The upper shuttle is in automatic service to Aisles 1 and 3 only. Pallet transfer to TD2 is not stable yet, but there are plenty of cells in 1 and 3! The speed seems fast, it keeps up easily We do not recommend operations personnel going up on the upper shuttle runway until more of the construction is completed. We told the operators if the upper shuttle goes down to leave it down and follow the normal call procedure. 2024-05-18 20:21:30 Not Assigned
453 BOPP_1 pallet was stuck half ways on transfer deck and shuttle, then pallet got twisted on stacker by operator put shuttle in manual and mover pallet, then had to climb on transfer deck to stacker and strain out pallet, took out Mauly, then shuttle would go to auto but wouldn't not move, moved shuttle to home position next to elevator conveyer, then had to clear mission, and restart pc 2025-12-19 14:33:06 Doro villegas
455 BOPP_2 case #455 missing rubber bumpers case #455 replace rubber bumpers for cross travel 2024-11-04 14:24:20 Eric licerio
456 BOPP_1 go to the 11 running stackers and get pictures of the currently installed AIM modules. It needs to show the serial number and model number on the front label. I've attached an example for your reference. Also, try to get a picture of the internals of each one where fire damage usually occurs. There's a second picture example. The front cover must be removed to get a good view of this area, so be sure to remove power before opening it 2024-06-05 08:14:55 tyler garza
457 BOPP_1 broken cable put back together with existing parts 2025-12-19 14:33:23 Doro villegas
458 BOPP_1 stacker got hung up on transfer deck wrong position, called Tomas he drove stacker up and out stacker would not move radio was unplugged, also had to adjust floor limits and sensors. ran one mission and happen again need to find out why this keeps happing 2024-08-12 15:26:39 Doro villegas
462 BOPP_2 #462 - bumper missing on northwest side. #462 - need to replace rubber bumper on northwest side. 2024-11-08 08:53:50 Eric licerio
465 BOPP_2 Line 15 would not boot up. PLC LOST PROGRAM, REPLACE CPU/PLC 2024-07-19 13:55:40 Thomas Learn
466 BOPP_1 Wrapper inverter Fault Wrapper had an inverter fault I reset the panel and cleared the inverter fault, then the conveyors started working again. 2024-06-03 15:07:02 tyler garza
467 BOPP_1 inside cart would not move check cable pully ,check track ,inverter kept going into fault disconnected cart 2025-12-19 14:33:41 Doro villegas
470 BOPP_2 #470 entry system turn table control box has loose switch #470 switch needs to be tightened 2024-08-13 15:39:44 tyler garza
471 BOPP_1 ERGON HIT ROLL LINE LOST POWER TO RECOVER POWER HAD TO LEVEL ERGON BACK OUT SO IT COULD HOME OUT THE WAS ABLE TO POWER UP AND PUT BACK IN AUTO 2024-06-19 07:24:45 Not Assigned
473 BOPP_1 ERGON HIT ROLL LINE LOST POWER TO RECOVER POWER HAD TO LEVEL ERGON BACK OUT SO IT COULD HOME OUT THE WAS ABLE TO POWER UP AND PUT BACK IN AUTO 2024-06-19 07:25:04 Not Assigned
474 BOPP_1 bay 4 broken chain got call from Alfredo that bay 4 had a broken chain. came in no issue. operator did say he had problem earlier with upper shuttle shitting there after unloading pallet and all he did was reset all good. 2024-06-27 07:52:29 Not Assigned
475 BOPP_2 crane 4 stopped got call from steven around 20:15 that crane 4 shut down. I reset crane all good. 2024-06-27 07:56:02 Not Assigned
476 BOPP_1 cradle hitting sensor that was too high on south cart east side lower sensor and test all good 2024-06-28 07:48:43 Not Assigned
482 BOPP_1 cradle hit sensor. south cart east side sensor was too high so cradle would hit it and stop. adjusted sensor test all good 2024-06-28 09:10:10 Not Assigned
494 BOPP_1 crane lost power and having mission issues. need to follow up, still have mission issues. 2025-12-19 14:34:02 Thomas Learn
495 BOPP_1 pallet crash fix no follow up 2024-07-03 20:52:15 Benjamin Leita
496 BOPP_2 shuttle wheels are falling a part need order new ones for spare YS N01 072-N WO # YE7079 CC # 6A03 operator found rover wheel on track and report to cma 2024-08-30 15:22:48 alfredo pinon
503 CFP Motor and Gearbox Upgrade Replace motor and gearbox on table 123 on north entry conveyors 2024-08-12 15:38:09 Joe Moya
504 BOPP_1 X2 travel brake fault on Stacker 1 Bopp 1 After checking the motor and the panel. I went to the computer and saw that there was a non-existent pallet. After deleting the pallet, I was able to fix the issue. Then I stayed until 5 missions went through with no fault. 2024-07-22 14:24:18 tyler garza
505 BOPP_2 Need to install Remote Relay to activate Slack Chain Bypass without the need to climb onto the crane. Parts are here and print is complete. Need installation. Relevant print pages attached. 2024-08-06 10:36:50 tyler garza
506 BOPP_2 Need to install Remote Relay to activate Slack Chain Bypass without the need to climb onto the crane. Parts are here and prints are complete. Need installation. Relevant print pages are attached. 2024-08-06 10:36:53 tyler garza
507 BOPP_1 Install remote relay to enable activation of the "Label Finished" pushbutton from the forktruck while sending re-entry pallets. Parts are here and print is complete. The relevant print page is attached. Just need installation. 2024-08-20 14:29:58 tyler garza
508 BOPP_1 it is not clear how the RDS works between client pc and server pc programmatically create a document to detail all steps on client/server operations. A draft is done on 7/22/24 2024-08-06 15:08:25 Yiduo Wang
509 BOPP_1 upper shuttle and bay 4 handshake not visible. hard to trouble shoot. create a sensor page for sensor handshake on ash to make it easier trouble shooting. still going. The upper shuttle sensor page is done 2025-12-15 14:34:54 Yiduo Wang
510 BOPP_1 East hoist drive shaft broke, dropped roll to the ground between cantilevers Remove hoist drive shaft and flange, reweld flange in shop, reinstall on crane, align. Shortly afterward the hoist encoder failed, presumably from the impact when the holder fell, replaced it, reworked coupling attachment to the hoist drive shaft, loaded parameters Ran test missions, looks normal Jumbo roll still needs to be picked up off the floor, the north locations are disabled for now 2024-08-02 08:49:33 Not Assigned
511 BOPP_1 Round 2 on Sunday 7/28 1. all hoist movement shuts down with Z trajectory error 2. later, slack chain and axis emergency prevents power up 3. later, hoist won't go all the way to the bottom position 4. later when running, putting a jumbo roll south into any cantilever stops with 'full error' 1. after troubleshooting, the encoder installed earlier today to replace the one damaged by the fall had itself failed. So installed third encoder for the hoist (Z axis), had trouble getting the parameters to stay loaded in the encoder 2. put arbitrary location value in encoder to start the calibration process, then hoist ran up when commanded to go down and ran too high into the overhead on the emergency limit and caused slack chain condition. Manually released brake to drift hoist down by gravity off of the emergency limit. Found arbitrary value entered in encoder was too large, that is why it would only go up even when commanded to go down. Calibrated encoder successfully at top 3. hoist would not move all the way to the bottom because the shuttle zone rotary switch was in the wrong position, in the shuttle area it only goes down to the shuttle height. Corrected position of shuttle zone rotary switch 4. At this point the crane would run automatic missions, except it could not put a jumbo roll into a cantilever toward the south. The 'forward blocked' alarm was being caused by the blue sensor that looks into the cantilever to prevent a roll to roll collision. That sensor had been hit during the original roll drop, broke the connector mounting but still worked. However, the internal switch for 'light on' and 'dark on' had somehow changed position and was creating the alarm. We replaced the sensor since the connector was damaged. Ran test missions, normal Followup--the dropped roll is still on the floor and that area disabled 2024-08-02 08:48:29 Not Assigned
512 CFP got call on Friday 7/26 for exit table 1 it would not roll in auto fixed chain put in auto ok 2024-08-05 15:35:31 Joe Moya
513 BOPP_1 P3 Dropped roll and cradles were not in same positions After looking at P3 found that east side hoist coupling was twisted off from the flange causing the roll to fall to the ground and the cradles misaligned after removing coupling Alfredo welded a piece of pipe to the coupling to give it same measurement as the original. Installed the repaired coupling back to P3 test was successful moved P3 crane to the south and as we were coming down to remove some straps that we had used to pull cradle up the crane went into alarm axis emergency form there we changed encoder, and it ran for about an hour then would go back into alarm after returning around 12:30 we replaced another encoder and put settings in and those would stay in encoder but for some reason the value would not after Glen arrived and entered a value that would let us move up and down See Glen's email for rest of second day of P3. 2024-07-29 09:20:15 Not Assigned
514 BOPP_2 test test 2024-08-05 16:22:43 Not Assigned
516 BOPP_2 Cables damaged from counterweight falling replacing z drive motor cable need to replace old damage z cable and install new 2024-09-03 13:08:08 Doro villegas
521 CFP Replace Y-axis encoder with SICK laser Replaced encoder and revised print 2024-07-30 10:06:34 Not Assigned
524 BOPP_1 SICK S300 sensor failed and cannot program Programming cable arrived. Learn to program the sensor 2025-12-19 14:34:17 Thomas Learn
525 BOPP_1 US/LS prints need revision Complete print revisions 2025-12-19 14:34:31 Thomas Learn
526 BOPP_1 Drice Cliq cables are routed through the panel door temp. after fire Re-route Drive Cliq cables 2024-08-05 13:46:46 Benjamin Leita
527 BOPP_1 Send failed AIM modules to siemens Waiting for RMA from Ken 2024-09-04 14:16:53 Thomas Learn
528 BOPP_1 Cradle positions are incorrect Investigate positioning problem with Bonfanti 2025-12-19 14:34:52 Thomas Learn
529 CFP #529 sensor brackets damaged after pallet crash #529 build new sensor brackets 2024-09-24 11:07:44 Joe Villarreal
530 BOPP_1 elevator overshot its destination for upper conveyer recovered by using bypass button and leveling out elevator put back in auto 2024-08-05 20:05:52 Not Assigned
531 BOPP_1 outside cart would not move laser had a fault, took off and cleaned put back in auto 2024-08-09 07:42:27 Not Assigned
532 BOPP_1 value was was off on encoder PT 100 could not connect PLACE SHUTTLE IN HOME POSTION, TOOK LIKE 20 MIN TO CONNET PT100 FOLLOW UP NEED TO REPLACE RIBBON & PT100 RIBON HAS A SHORT & PT100 COULDNT READ INFO 2024-08-12 14:57:47 Benjamin Leita
533 BOPP_1 Replace travel drive with 755, 40 amp 1. Prepare electrical drawing 2. Prepare parameter list 3. Order replacement drive including internal cards 4. Schedule replacement including raising drive wheels off rail for rotation tuning 2025-12-19 14:35:18 Glenn Hasdorff
534 CFP 534 counterweight block has bad blocks counterweight leaning to far one was hitting panel frame. replace blocks or brass and order spare parts 2025-03-31 14:17:10 Joe Villarreal
535 CFP 535 counterweight block has bad blocks counterweight leaning to far one way replace blocks or brass and order spare parts 2025-12-22 14:08:58 Joe Villarreal
536 CFP The wrapper would only wrap about 1 or 2 times and then stop. the wrapper was also not cutting the plastic due to the wrapper not completing its process After trouble shooting i was able to locate that it was a sensor, after adjustment I watched the wrapper work on a total of 5 pallets before heading home. 2024-08-15 14:28:35 tyler garza
537 BOPP_1 A mission that was deleted was still stuck in the system, causing entry to come to a stop. After checking all the sensors and trying to clear pallets, my last option was to call Glenn and then he was able to resolve the issue in the system. 2024-08-16 10:27:19 tyler garza
538 BOPP_1 Saturday night i got a call in for BOPP 1 Entry they tried deleting a pallet from the system, but it never deleted. The first thing I did when I came in was check all sensors and look at the program after trouble shooting, I came to realize that the only way to fix the issue was to call Glenn. then he could manually delete the mission from his computer. But unfortunately, the computer that he needed to connect to was not running. So, I had to wait for Glenn to get here, once he was here, we were able to recover through the system. I then proceeded to watch 4 or 5 mission go through and be delivered before leaving for the night. 8-16-2024 2024-08-19 08:40:35 tyler garza
539 BOPP_1 Entry in BOPP 1 tried to drop off a pallet on transfer deck 2 but for some reason the motor stopped working on the transfer deck and the upper shuttle wasn't able to fully deliver the pallet onto transfer deck 2. After finding transfer deck 2 how it was and the upper shuttle first thing, I did was put the transfer deck 2 into Manuel. I then proceeded to try to move the pallet farther north into the transfer deck, the motor was not responding so I went and got a strap, and a come-along. i put the strap through the pallet and proceeded to pull the pallet over about 2 inches so then the upper shuttle was able to move. After that I had to call Glenn to delete missions within the system so the upper shuttle would pick up missions again. After Glenn was done the upper shuttle was fixed and I proceeded to watch 4 or 5 missions before heading home. The transfer deck 2 entry motor needs a follow up I was not going to risk getting hurt while up there, this issue did not affect entry for the rest of the weekend. 2024-08-20 14:29:54 tyler garza
540 BOPP_1 The Entry System in BOPP 1 The operators tried to delete a mission, but it did not work I came in trouble shooting the program and the sensors, then came to realize that Glenn was needed again to erase the mission from inside the system. After he did that, the upper shuttle delivered pallets after the 2nd attempt to send a pallet. it took a little longer because there were a couple missions deleted that we had to recover from. After the issue was resolved I watched 4 missions go thru and then headed home. 2024-08-19 09:08:34 tyler garza
541 BOPP_1 BOPP 1 Entry a sensor blinked as a pallet was loading onto the upper shuttle causing it to get stuck halfway on the shuttle and halfway on bay 4. I was able to adjust the sensor and get it moved over on the shuttles right position, Then Glenn proceeded to fix the missions through the system. After that the mission wanted to go to transfer deck 3 lane B, but the transfer deck was at lane A.So i went down to the transfer deck and moved it over to Lane B hoping that it would complete the mission. that messed up the mission then causing me to have to manually take off the pallet. After that we were able to recover from the issue, i then watched 4 pallets go through before leaving. 2024-08-19 09:35:12 tyler garza
542 BOPP_1 BOPP 1 Entry Upper Shuttle, me and Glenn came to the decision that a pallet had to of hit a sensor causing this issue. When I came in I found a sensor on the north side of the upper shuttle that looked to be hit by a pallet, causing another mission to not fully go onto the upper shuttle. After fixing the sensor and making sure it would not blink again Glenn was able to recover Through the system and I then proceeded to watch 5 or so missions go through before leaving last night. 2024-08-19 09:39:59 tyler garza
543 CFP Over temperature on the Active Interface Module Date: 8/1/24 and again 8/8/24 First module that was replaced was one that had been repaired Replace with new module and sent damaged one to Paul Lopez 2024-08-20 14:54:15 Joe Moya
544 CFP Transformer failed was for 220v and 110v Replace 480v to 24v 20 amp power supply for X- axis brakes and one 480v to 24v 40 amp power supply for Y axis brakes 2024-10-28 09:42:14 Joe Moya
545 CFP Active interface module caught fire Infeed not ready 8/16/24 Found that the active interface module had failed and burnt replaced module tested than to automatic 2024-08-20 14:54:07 Joe Moya
546 BOPP_1 P2 Ground panel A/C unit is creating excessive condensation. Many 5gal bottles are there already full. Operators are opening the panel door believing it will help. Check filters on the a/c unit and try to determine the cause of excessive condensation. Replace unit if or install drainage solution if needed. 2024-11-04 14:26:44 tyler garza
547 BOPP_1 547 loose chains on entry chain tables: because no adjustment for chain tension you will need to remove links. 547 loose chains on entry chain tables: because no adjustment for chain tension you will need to remove links. 2025-12-19 14:35:40 alfredo pinon
548 BOPP_1 548 Bp1 entry Bay 4 chain table has broken pillow block bearing 548 Bp1 entry Bay 4 chain table: replace pillow block bearing 2025-12-19 14:36:25 Benjamin Leita
549 BOPP_1 549 Bp1 entry chain table: drive chain table is worn needs to be replaced. 549 Bp1 entry chain table ( this table is part of the alignment table ). we adjusted what we could but the chain is worn and needs to be replaced. not a rush 2025-12-19 14:36:08 Eric licerio
550 BOPP_1 Line 3 crane panel screen stopped working They said Line 4 was down until Monday, so I took the panel view from Line 4 and swapped it onto Line 3 so, they were able to continue to run for the rest of the weekend. 2024-08-26 14:16:03 tyler garza
551 BOPP_1 Line 3 crane panel screen stopped working They said Line 4 was down until Monday, so I took the panel view from Line 4 and swapped it onto Line 3 so, they were able to continue to run for the rest of the weekend. 2024-08-26 14:16:04 tyler garza
552 BOPP_1 Line 3 crane panel screen stopped working They said Line 4 was down until Monday, so I took the panel view from Line 4 and swapped it onto Line 3 so, they were able to continue to run for the rest of the weekend. 2024-08-26 14:16:09 tyler garza
553 BOPP_1 550 upper shuttle found some mounting bolts loose on chain arms. 550 upper shuttle: add lock washers 2025-12-19 14:38:01 Benjamin Leita
554 BOPP_1 554 upper shuttle: panel filter cover is missing a bolt 554 upper shuttle: looks like threads are striped out on cove frame. need to rethread or replace. 2025-12-19 14:37:49 tyler garza
555 BOPP_1 555 entry system: control stations need new labels 555 entry system: control stations need new labels. 2025-12-19 14:38:23 tyler garza
556 BOPP_1 556 trandeck1: upper bay drive sprockets are not aligned. 556 transdeck1: upper bay drive sprockets are not aligned need to shift sprocket on drive shaft. done by eric and tyler & alfredo put new bearings on idle sprocket 2024-08-30 15:25:05 Eric licerio
557 BOPP_1 557 transdeck1 upper bay: idle tension sprocket has bad bearing. 557 transdeck1 upper bay: replace bearing 2024-09-10 15:00:33 Not Assigned
558 BOPP_1 558 transdeck1 lower bay: drive shaft bearing is missing bolts. 558 transdeck1 lower bay: add bolts 2024-10-09 15:26:21 Joseph Prusick
560 BOPP_1 560 transdeck1: water in the trench. 560 transdeck1: remove water. 2024-11-08 08:53:30 Eric licerio
561 BOPP_1 561 JRSHUTTLE BUSBAR: Busbar transfer funnel east of forklift crossing is worn. 561 JRSHUTTLE BUSBAR: Funnel needs to be replaced. 2025-12-19 14:40:23 Benjamin Leita
562 BOPP_1 562 stk1 J-Box on platform missing top cover. 562 stk1 J-Box replace cover 2025-12-19 14:39:55 Joseph Prusick
563 BOPP_1 563 stk1 480 brushes are worn down. 563 stk1 480 brushes need to be replaced. 2024-12-30 13:47:19 Joseph Prusick
571 BOPP_1 571 transdeck2: panel fan does not work. 571 transdeck2: repair or replace fan. 2024-10-09 15:25:47 Joseph Prusick
572 BOPP_1 572 transdeck3: upper bay idle chain sprocket has bad bearing. 572 transdeck3: upper bay replace idle chain sprocket. 2024-12-09 10:39:59 Eric licerio
575 BOPP_1 575 transdeck3: panel fan missing 575 transdeck3: install fan in panel. 2024-10-09 15:25:25 Joseph Prusick
576 BOPP_1 576 trasdeck3: drive coupling, south side flange is separated from pipe 576 trasdeck3: remove coupling weld back together 2025-12-19 14:27:52 alfredo pinon
577 CFP was giving a drive fault will run but still every 4-5 pallets it will give fault, made use manual wrapper 2024-10-28 09:42:09 Joe Moya
578 BOPP_2 outside shuttle would not move check breakers ,power flex and fusses found this in track, a tool from the operators 2024-08-30 08:05:25 Not Assigned
580 BOPP_1 580 stk3 busbar north side is missing the cover 580 stk3 busbar add cover 2024-11-04 14:26:51 tyler garza
581 BOPP_1 581 stk3 y motor cover missing wires exposed. 581 stk3 y motor install cover 2024-10-09 15:25:11 Joseph Prusick
584 BOPP_2 Cables damaged from counterweight falling replacing DAMAGE control cable pulled out old control cable and pulled in new control and terminate both ends 2024-09-03 13:07:43 Doro villegas
585 BOPP_1 broken roller easy out broken bolt and fixed chain to roller 2024-09-03 11:34:59 Not Assigned
586 BOPP_1 pallet stuck on half ways on upper shuttle finished taking pallet off of shuttle manually, had to get Tomas to delete stuck mission on shuttle need to take pallet off of tranferdeck and look at sprockets and chain 2024-10-08 08:32:15 Joseph Prusick
587 BOPP_1 clamps would not open found a table bad sensor /then found a bad sensor on wrap machine the air hose had a leak, and someone unscrewed the air pressure 2024-09-03 11:45:04 Not Assigned
590 BOPP_1 table 3: there are two reflector brackets with broken welds need to remove and weld 2024-11-08 13:40:36 Joseph Prusick
591 BOPP_1 table 2: blue sick sensor mounting bracket, one of the 2 bolts are stripped making it easier for the sensor to move around. replace mounting bracket. 2025-02-26 08:50:58 Joseph Prusick
592 BOPP_2 Tue.Got called from bopp1 shipping pallet not moving When I got here Lupe ask what did I do Isaid nothing just got here she said oh it been running well asked to put more missions in so I could watch. Watched next 3 missions and did not see any problems so I left 2024-09-09 08:18:40 Not Assigned
593 BOPP_2 CFP wrapper shutting off Came in found wire to carriage limit was rubbing against roller causing it to short Taped up put back in auto watched pallets Follow up: replace emergency limit and rewire 2024-10-28 09:41:56 Joe Moya
594 BOPP_2 Entry system having 2 of the same UDC on upper shuttle Found bad handshake sensor replaced hard wired sensor with M12 connector sensor still doing same thing after talking to Glen found out that sensor had shorted output point for sensor after replacing output point and Glen changed it in program It was working back to auto 2024-09-09 08:41:41 Not Assigned
595 BOPP_1 Packing crane would not go north after trouble shooting for about an hour Rosevelt said that he was not in a bind for it and that line 4 was not running that they were just running some sort of test chart for gloebel 14 after found that out I told him I was going to leave it down. 2024-09-09 08:50:52 Not Assigned
604 CFP 604: STK1 SOUTH X DRIVE COUPLING. GEARBOX COUPLING AND CHAIN IS BAD REPLACE COUPLING AND CHAIN 2024-09-18 08:58:29 Joe Villarreal
607 CFP 607 STK4 HOIST G/B COUPLING AND CHIAN IS WORN OUT REPLACE COUPLING AND CHIAN 2025-02-03 11:23:51 Joe Villarreal
608 CFP 608 STK1 SOUTHEAST X LOWER GUIDE BEARING IS BAD REPLACE GUIDE BEARING 2024-10-25 09:38:51 Joe Villarreal
609 CFP 609 STK1 EXIT BAY ROLLER TABLE CHAIN GUARD DAMAGED NEEDS TO BE REPLACED BUILD AND REPLACE CHAIN GUARD 2024-10-25 08:42:35 Joe Villarreal
610 CFP 610 DAMAGED LIGHT STACK ON EXIT BAY 1 CONTROL BOX REPAIR OR REPLACE LIGHT STACK 2024-09-16 13:45:58 Joe Moya
613 CFP 613 stk2 platform j box cover missing bolts replace bolts 2026-03-25 08:25:20 Joe Moya
614 CFP 614 stk2 exit bay reflector bracket bolt broken replace bolt 2024-09-24 14:59:57 Joe Villarreal
615 CFP 615 480 brushes low replace 2024-10-28 09:41:37 Joe Moya
616 BOPP_1 call in packing crane 41 19:00: hoist wire rope unspooled. found stuck down contact contact working and spooled wire rope back on drums. had to adjust high and low positions. follow up: check contact and high and low position 2024-10-08 08:10:42 Not Assigned
617 BOPP_1 CALL IN 3:20 JR SHUTTLE STOPPED BETWEEN LINE 2 AND 3 AND WILL NOT MOVE. OPERATOR DID SAY THAT THE SHUTTLE WAS LOSING VALUE AND RUNNING SLOW. AFTER TRING TO GET COMMUNICATIN BACK AND FAILED I DID FIND A PLUG FOR COMMUNICATION ON THE CPU THAT WAS VERY LOOSE SO I PUSHED BACK IN AND TIGHTEN DOWN BUT STILL NO COMMUNICATION. SO, I CALLED FOR HELP. I STARTED TO TRY TO MOVE SHUTTLE IN MANUAL TO BRING IT BACK TO HOME POSISTION BUT IT WOULD NOT GO WEST THATS WHEN I NOTICED THE VALUE SHOWED THAT IT WAS ALREADY AT HOME POSITION. SO, AFTER RESETING A COUPLE TIMES I GOT THE SHUTTLE BACK TO WARHOUSE. GLENN CAME IN TO HELP AND AFTER WORKING ON IT HE NOTICED THAT THE SETTING IN THE ENCODER HAD CHANGED. WE PUT THE CORRECT NUMBER BACK IN AND THE SHUTTLE RAN GOOD. 2024-09-20 09:19:09 Not Assigned
618 BOPP_2 call in line 15 15:30: cable carrier broken on outside cart. repair cable carrier. called Joseph on to help. 2024-09-23 08:09:32 Not Assigned
619 BOPP_1 will not power up and will not go into auto adjusted x-axis offset 2024-10-08 08:28:37 Joseph Prusick
620 BOPP_1 crane going into alarm need to replace centering sensor 2024-10-08 08:29:23 Joseph Prusick
621 BOPP_1 P-3 crane going into alarm, call in at o245 Found bad centering sensor 2024-09-30 09:20:50 Benjamin Leita
622 BOPP_1 Call in at 0730 Sunday. Will not power up. found bad fuse, replaced fuse. 2024-09-30 09:24:22 Joseph Prusick
623 BOPP_1 TD3 (NOT stacker)--PC10 cannot talk to TD3 by serial, reason unknown-- Clue #1--Intermapper shows 'no snmp v1 response' from Digi inside TD3 (interesting but not conclusive, so take a closer look at the Digi inside TD3) Clue #2--ping to 172.22.14.65 works. This proves the Digi is not dead and the network path to the Digi in TD3 is working Clue #3--the Digi 'device discovery' utility shows 172.22.14.65 on the list but with no name (interesting but not conclusive) Clue #4--browser window to 172.22.14.65 brings up the Digi login box but the credentials do not work. (Now we're getting somewhere, that suggests at least part of the configuration in the Digi was lost) Clue #5--the factory default credentials do work (That confirms that the configuration was lost and the Digi had gone back to default state except for the network address which is stored separately) Repair steps: #1--Restore the configuration using the backup file Thomas had prepared a year ago (now the PC10 can talk to the TD3 Easy again!!) #2--Add the SNMP community name in the Digi configuration (not needed for the process but it makes Intermapper display the Digi correctly, so now Intermapper shows the Digi) #3--make a new backup file including the SNMP setting which we had added after Thomas' previous backup All done, fix the missions, bring down one pallet, etc. 2024-09-30 17:02:33 Thomas Learn
624 CFP test test 2024-10-08 10:47:54 Not Assigned
625 CFP test 2 test 2 2024-10-08 10:54:05 Not Assigned
626 CFP test 3 tes 3 2024-10-08 11:03:33 Not Assigned
627 BOPP_1 got called Friday that Cradles would not move out onto conveyor found a sensor that was damaged the top part of the sensor was broken off replaced watched run ok 2024-10-21 08:17:21 Not Assigned
628 BOPP_1 got called Saturday that pallet got twisted and damaged sensors Got here and found that 8 sensor brackets bent and unistrut that holds 2 of the sensors had broken off heated them up with torch got them as straight as possible and welded the unistrut back up fixed position of sensors test ok. Follow up: check sensor brackets may need to be replaced also ty-rap sensor wires back did not do that because brackets were still warm when finished 2025-04-22 08:50:49 Joseph Prusick
629 CFP Blowen fuse and siemens power 20 amp replace panel and clean up control left over items 2026-03-25 08:24:24 Joe Moya
630 BOPP_1 #1 operator Javier call for JR shuttle loss power hi found plastic material on the power buss bar brushes #2 hi try to power up but nothing work for him #3 i found trip main backer on mcc room re set power #4 power the shuttle move on manual and work for auto re set panel on mcc room to power shuttle back and it works just fine some brushes need to be replaced alfredo pinon call from 10:15 to 11;50 PM 10/25/2024 2024-11-11 15:11:42 Not Assigned
631 BOPP_1 Alfredo's call 10\26\2024 9:30 pm to 11:30 pm pallet island operator call #1 hi report that bypass table stop working #2 found trip braker on panel : motor tested good #3 re set braker on panel reboot power and still trip the braker desire to live it down operator can still operate wit out the bypass table 2025-04-22 08:51:13 Joseph Prusick
632 BOPP_1 Alfredo's call 10\27\2024 9:00 am to 10:15 #1 operator call saying cant not re set or start wrapper machine #2 i found busted main air line from air regulator to cutting arm just replace air house and after that was able to re set wrapper #3 back in service need order new air supplies material for spare parts 2025-12-19 14:26:28 Benjamin Leita
633 BOPP_2 Crane 1 went down just before midnight on the Monday night shift. Two alarms for travel drive ‘X1’ were repeating continuously on the screen: 23:43:51:682| COMM LOSS TO X1 TRAVEL DRIVE (INV2, R2) 23:43:53 10/28/24 23:43:52:807| X1 DRIVE HAS FAULT-GO TO "INPUTS" SCREEN FOR RESET 23:43:54 10/28/24 The 1203-GD1 module associated with the X1 drive was showing a red light on it which is not normal. To confirm that the drive was not the cause of the problem, we moved the working 1203-GD1 module from the X2 drive to the X1 drive (with address changed) and it worked there. That proved the X1 drive was ok and only the 1203-GD1 module had failed. Paul located a replacement 1203-GD1 module and Joseph installed it, setting up the switches on the replacement module per the instructions on the print. That restored the crane to operation. 2024-11-01 15:26:32 Not Assigned
635 BOPP_2 Case# 635 Packing crane 23 east alignment arm is bent. It needs to be straighten out. Case# 635 Packing crane 23 east alignment arm is bent. It needs to be straighten out. 2024-11-06 14:49:57 Joe Villarreal
644 BOPP_2 #644 packing crane 22 air is damaged Reroute air line to the east side. 2024-12-19 11:01:55 Doro villegas
654 BOPP_2 pallet island pallets would run all the way and stop before getting to scale the issue was someone changed the setting on the panel. Anytime you need to send the pallets to the scale table the panel needs to be set at 6.01 for it to run pallets to scale with no issues. 2024-11-07 10:30:54 Doro villegas
662 BOPP_2 Case 662 packing crane 25 open close cable carrier missing boat. Add bolt. fix done 2025-09-03 14:44:31 alfredo pinon
671 BOPP_2 Case 671 line 16 south west elevator cradle return sensor bracket is missing a bolt so bracket moves round. Install bolt 2024-12-03 14:28:27 Not Assigned
672 BOPP_2 Case 672 line 16 south east elevator cover missing bolts Install bolts 2024-12-03 14:28:48 Not Assigned
674 BOPP_2 Case 16 line 16 north west elevator cable carrier bracket damaged Repair 2025-12-01 08:52:15 Doro villegas
677 BOPP_2 Case 677 crane 2 onboard panel light dose not work. Fix 2025-12-01 08:53:01 Doro villegas
681 BOPP_2 Case 681 crane 4 west arm wire connection nut damaged. Replace 2025-12-01 08:53:36 Doro villegas
689 BOPP_2 Case 689 Wrapper roller table sprockets worn Replace 2025-12-01 08:48:51 Doro villegas
690 BOPP_2 Case 690 Wrapper roller table has chain stretch Replace 2025-12-01 08:50:10 Doro villegas
691 BOPP_2 Case 691 Wrapper clamps jbox damaged Replace 2025-12-01 08:49:42 Doro villegas
693 BOPP_2 Case 693 entry light Fix 2024-12-03 14:38:12 Not Assigned
694 BOPP_2 Case 694 Reentry table damaged sensor bracket. Replace 2024-12-03 14:38:32 Not Assigned
695 BOPP_2 Case 695 48 piller jbox damaged Fix 2024-12-19 10:55:32 Doro villegas
697 BOPP_2 Case 697 upper shuttle x drive rocking Check offset 2024-12-10 08:24:00 Doro villegas
698 BOPP_2 Case 698 Bp2 upper shuttle cable is to tight and is rubbing on frame digging into cables. Create slack and secure cables 2024-12-19 11:00:09 Doro villegas
699 BOPP_2 Case 699 Entry tables 1,2,3 have chain slack Tighten 2024-12-17 08:31:57 Eric licerio
701 BOPP_2 Case 701 Table d drive sprocket shifted over digging into frame. Make sure it doesn't shift back if so may need to put a tac on shaft. 2024-12-03 14:43:16 Not Assigned
704 BOPP_2 Case 704 Table c north and south west upper wheels missing Replace 2025-12-01 08:51:08 Doro villegas
705 BOPP_2 Case705 Table c n/e lower wheels have flat spots Replace 2025-12-01 08:47:39 Doro villegas
706 BOPP_2 Case 706 Table b n/e wheel has flat spot Replace 2025-12-01 08:47:10 Doro villegas
707 BOPP_2 Case 707 Table b bolts missing on east and west side for cylinders Replace 2024-12-03 14:44:48 Not Assigned
709 BOPP_2 Case 709 Stk3 brush collectors worn Replace 2024-12-03 14:28:00 Not Assigned
710 BOPP_2 Case 710 Stk3 n/e sensor arm bolts are stripped Replace 2024-12-03 14:45:29 Not Assigned
711 BOPP_2 Case 711 Stk3 + feed button doesn’t work Fix 2024-12-03 14:45:45 Not Assigned
712 BOPP_2 Case 712 Stk1 brushes worn Replace 2024-12-03 14:46:00 Not Assigned
713 BOPP_2 Case 713 Stk1 fork top section bearings missing Replace 2025-12-01 08:45:50 Doro villegas
715 BOPP_2 Case 715 Stk1 west counterweight blocks worn. Replace 2025-09-03 14:44:03 alfredo pinon
717 BOPP_2 Case 2 Stk2 siron not working Fix 2024-12-03 14:47:11 Not Assigned
718 BOPP_2 Case 718 Stk2 fork gearbox leaking Replace 2025-09-03 14:45:06 alfredo pinon
719 BOPP_2 Case 719 Stk2 din rail loose because back plate threads are stripped. New hole 2024-12-03 14:49:43 Not Assigned
720 BOPP_1 Carl reported 'cutting off'. Found 5 volt level was not stable, varied from 5.2 to almost 6 when tapping on power supply Removed supply, tightened every connection, reinstalled and set voltage correctly, now stable when tapped on. 2024-12-13 05:35:29 Not Assigned
721 BOPP_1 Carl reported 'cutting off'. Found 5 volt level was not stable, varied from 5.2 to almost 6 when tapping on power supply Removed supply, tightened every connection, reinstalled and set voltage correctly, now stable when tapped on. 2024-12-13 05:35:33 Not Assigned
722 BOPP_1 Pallet twisted at transition from entry bay to upper shuttle Removed pallet in poor condition. Noted that entry bay and upper shuttle conveyors are not at the same elevation. Every pallet drops down from entry bay to shuttle, so imperfections on pallets are more likely to make them go crooked 2025-02-20 10:20:51 Not Assigned
723 CFP film breaker 1. check settings 2. adjust sensor and cam 3. check dancing arm in home pos. manually move arm so motor can spin. 4. replace dancing arm sensor. 5. check brushes because we started to get p012 fault on inverter. over voltage 6. replace inverter. 7. found damaged cable on up down carriage for dancing arm. 8. replace cable with tray cable we had. 9. follow up replace cable with correct flex cable. 2025-02-12 08:39:45 Joe Moya
724 BOPP_2 shuttle was losing power found 2 bad contacts and replaced 2025-01-22 14:37:50 Not Assigned
725 BOPP_1 Call-in BOPP-1 pallets would not enter wrapper. Found that pallets present sensor was dirty. clean sensor. 2025-01-25 20:25:45 Benjamin Leita
726 BOPP_1 call-in operator said jumbo shuttle keeps losing encoder value. I watch j/r shuttle run six missions. All was good. I did notice one time a roll coming out of the warehouse, it moved the shuttle around causing it to come off the centering px. 2025-01-26 09:31:56 Benjamin Leita
728 BOPP_1 c-hook crane: Travel Bumpers missing Replace 2025-04-01 14:19:32 Joseph Prusick
729 BOPP_1 line 12 single roll cart: Cable carrier damaged Line 12 single roll cart cable carrier is too short need to add more sections to prevent from breaking 2025-04-22 08:49:35 Joseph Prusick
730 BOPP_1 Button is backwards. Open is close and close is open. Org. 11 packing crane remote open/close button are backwards 2025-02-20 10:17:08 Not Assigned
731 BOPP_1 Open limit is missing arm Replace arm or limit. 2025-12-19 14:26:02 Joseph Prusick
734 BOPP_1 West arm sensor damaged but working FYI: 2025-12-22 14:05:48 Benjamin Leita
736 BOPP_1 Travel bumpers missing Replace 2025-02-20 10:13:34 Not Assigned
737 BOPP_1 Travel bumpers missing Replace 2025-04-01 14:18:32 Joseph Prusick
738 BOPP_1 packing crane 14: No lower limit crane can hit the ground. We made adjustments but you need to make sure low position is okay. 2025-12-19 14:24:55 Joseph Prusick
739 BOPP_1 West arm missing bolts on cover. Install bolts 2025-12-22 14:36:46 Joseph Prusick
740 BOPP_1 West arm sensor missing nut Install nut 2025-12-19 14:23:46 Joseph Prusick
741 BOPP_1 Trolley motor making noise when changing to low speed Fyi 2025-12-19 14:24:11 Joseph Prusick
742 BOPP_1 02\04\2025 10:15pm to 11:38pm Alfredo pinon get call from Rey operator saying that the wrapper the arms that hold the film dont work properly #1 found busted air line busted under the combeyor #2 also busted air line for the cylinder for the arms that hold the film #3 replaced 2 air lines total need replaced all lines after get that fix test good for auto 2025-12-19 14:22:54 Benjamin Leita
743 BOPP_1 operator carl report that P-2 crane loose power wen traveling on auto and cant not recover 02\06\2025 alfredo pinon from 7:38 to 8:38 i found a full roll on crane of center during rotation and hit the up and down legs wen was rotating on auto i bypass some sensors to recover crane and re set brakers inside of panel to get power back 2025-12-19 14:22:32 Benjamin Leita
744 BOPP_1 alfredo i get call from operator to CFP wrapper wrapper of of settings need to re set 2025-02-12 08:39:35 Joe Moya
745 BOPP_1 alfredo i get call from operator to CFP wrapper 02\08\2025 7:42pm to 8:30 pm wrapper of of settings need to re set 2025-02-12 08:39:31 Joe Moya
746 BOPP_1 operator ray call for entry no communication alfredo call on 02|08\2024 8:00 to 9:00 pm call for help to yidow and got it going on after 2025-02-10 07:14:57 Not Assigned
747 CFP operator GLOW call saying stacker #5 not responding manual operations i try to also in manual and don t respond commanders from remote alfredo call 02\09\2025 11:15 to 12:00 need to re set alarm on program 2025-02-20 13:50:22 Thomas Learn
748 BOPP_1 Elevator: when over hang sensor is blocked you can move elevator up and down and slow down and stop sensors do not work. Program change. 2025-12-19 14:22:10 Thomas Learn
750 BOPP_1 Bypass table missing rib and spring clip Order and replace 2025-04-22 08:48:56 Joseph Prusick
751 BOPP_1 Entry table missing spring clip. Order and replace. 2025-04-22 08:48:43 Joseph Prusick
752 BOPP_1 Entry table missing spring clip. Order and replace. 2025-04-22 08:48:31 Joseph Prusick
754 BOPP_1 No labels on control station Add labels 2025-12-22 14:06:17 Benjamin Leita
755 BOPP_1 Entry panel filter cover damaged Replace 2025-12-19 14:21:31 Benjamin Leita
757 BOPP_1 Table drive chain loose Remove link 2025-12-19 14:20:57 Benjamin Leita
758 BOPP_1 P2 crane: northeast bumper missing Replace 2025-12-22 14:04:24 Joseph Prusick
759 BOPP_1 P2 crane: ground panel siren not working. Fix 2025-12-19 14:39:19 Joseph Prusick
760 BOPP_1 P2 crane: onboard ac no filter. Fyi 2025-12-22 14:03:50 Joseph Prusick
761 BOPP_1 P2 crane: onboard panel doesn’t work. Repair or replace 2025-02-26 08:47:28 Joseph Prusick
762 BOPP_1 P2 crane: onboard panel doesn’t work. Repair or replace 2025-02-26 08:47:32 Joseph Prusick
764 BOPP_1 P2 crane: chain slack arm did not come off of sensor west side. Fyi 2025-12-19 14:20:13 Joseph Prusick
765 BOPP_1 P3 crane: onboard panel fan not working. Replace 2025-04-01 14:16:25 Joseph Prusick
766 BOPP_1 P3 crane: onboard panel fan not working. Replace 2025-04-01 14:16:14 Joseph Prusick
768 BOPP_1 P5 crane: both chain slack arms do not come off sensor. Fix 2025-02-26 08:42:49 Joseph Prusick
770 BOPP_1 P1 crane: ground panel fan not working. Replace 2025-04-22 10:12:22 Joseph Prusick
772 BOPP_1 Line 11: panel missing fan Fyi 2025-04-22 08:44:31 Joseph Prusick
773 BOPP_1 Line 11: south shuttle wheel flanges worn. Fyi 2025-12-19 14:18:48 Benjamin Leita
774 BOPP_1 Line 14: panel fan damage Fyi 2025-02-26 08:38:24 Joseph Prusick
777 BOPP_1 Line 14: north east shuttle estop Fyi 2025-02-14 11:27:31 Not Assigned
780 BOPP_1 had to adjust sensor on the chain slack adjuster. looked like it was bumped and was knocked down a little. was told by carl the next morning that it had no issues since. no follow up action needed 2025-02-20 08:55:04 Not Assigned
781 BOPP_2 call in: pallet would not move from scale. 1. after checking sensors and table. no issues found 2. called thomas to look at system. no issue found 3. yiduo and karl no problem found 4. removed all pallets from table and started over. still not working. 5. shift change Palla went to w/h opened team viewer reset data base and it worked. 2025-02-24 08:22:15 Not Assigned
782 BOPP_1 call in: entry roller alignment chain broken. two issues 1. broken chain. chain needs to be replaced. 2. two bolts broken on motor. 2025-03-03 14:51:01 Not Assigned
783 BOPP_1 TD 1 missing bumper Replace bumpers 2025-12-19 14:17:58 Eric licerio
784 BOPP_1 Stk1 panel fan doesn’t work. Repair or replace 2025-04-01 14:15:39 Joseph Prusick
785 BOPP_1 480 funnel bad deep groves. Replace 2025-04-01 10:05:41 Joseph Prusick
786 BOPP_1 Stk1 480 ground brush bad Replace 2025-04-01 10:05:24 Joseph Prusick
787 BOPP_1 TD1 upper bay loose chain Remove links 2025-09-03 14:43:37 alfredo pinon
788 BOPP_1 Missing bumpers Replace 2025-12-19 14:17:42 Eric licerio
789 BOPP_1 Hydraulic leak. Fyi 2025-12-19 14:37:26 alfredo pinon
790 BOPP_1 Hydraulic hose leak Fyi 2025-12-19 14:37:07 alfredo pinon
791 BOPP_1 Hydraulic leak Fyi 2025-12-19 14:36:50 alfredo pinon
792 BOPP_1 Up down arm idle bearing bad Replace done 2025-03-25 07:23:11 alfredo pinon
793 BOPP_1 Up down arm bolt hex head missing Replace 2025-09-03 14:44:49 alfredo pinon
794 BOPP_1 Bad filter Replace 2025-12-19 14:16:27 Joseph Prusick
797 CFP Exit bay 2 has bad idle sprocket Replace 2025-04-01 13:14:25 Joe Villarreal
800 CFP Exit bay 4 bad idle sprocket Replace 2025-03-07 13:57:58 Joe Villarreal
804 BOPP_1 chain busted replaced 10 ft cause chain was twisted 2025-03-17 10:16:38 Not Assigned
805 BOPP_1 Pallet not transferring onto upper shuttle Got called from Rey pallet island BOPP 1 he said that there was a twisted pallet on shuttle so he took down aborted mission and shuttle then he sent another pallet up and that shuttle would not pick up. So when I get here and I as well tried to abort everything and nothing happened well the program still showed that there was a pallet on shuttle. Is all I did was restart the program and pallet went away sent another up and worked. Follow up: find out why when you abort shuttle it does not remove pallet. 2025-12-19 14:16:14 Not Assigned
808 CFP Bad hoist encoder pulley Replace 2026-03-02 13:53:36 Joe Villarreal
809 CFP East bottom counterweight block bad Replace 2025-05-21 14:40:32 Joe Villarreal
811 CFP South x motor coupling bad Replace 2025-05-21 14:40:20 Joe Villarreal
812 BOPP_2 Called from BOPP2 Crane4 Height position sensor not making Came adjusted bracket because sensor was move all the way down already so move bracket about 1/4 inch up so sensor will make and checked distance to cantalever looked good back to auto watched mission good 2026-03-02 13:46:22 Not Assigned
814 BOPP_1 Got called packing cranes would not open Troubleshooting for awhile but did not fix left down moved back up to 13 for them to use Folow up check packing 14 for not opening 2025-12-19 14:15:58 Not Assigned
815 CFP Got called that pallets stoping in middle of conveyor adjusted sensor seemed to work then gearbox sounded funny Found gearbox making noise but still moving also cutting arm clamp needs to be replaced Follow up change gearbox and install clamp for cutting arm 2026-03-02 13:46:07 Not Assigned
816 CFP Got called that pallets stoping in middle of conveyor adjusted sensor seemed to work then gearbox sounded funny Found gearbox making noise but still moving also cutting arm clamp needs to be replaced Follow up change gearbox and install clamp for cutting arm 2026-03-02 13:45:57 Not Assigned
817 BOPP_2 operator call and report that was sprocket under the wrapper conveyor found broken bolt that hold the sprocket on place get new sprocket bolts and adjust the chain in place ready for automatic wit not problem 2025-03-25 07:29:14 Not Assigned
818 BOPP_1 operator report that p-3 panel don't power up re set panel for 15 minutes and then work 2025-03-28 07:39:18 Not Assigned
819 CFP 3\24\2024 operator report tat sprocket under the combeyor and Brocken chain found new sprocket with bearings and put chain back together ready for auto 2025-04-01 07:44:09 Not Assigned
820 CFP 3\26\2024 operator calling saying cant power up P-3 re set power on boar and on ground got it working back to automatic 2025-04-01 07:47:51 Not Assigned
821 CFP 3\26\2024 bopp1 upper shuttle operator report nothing move on manual found bad current collectors and replaced all 2025-12-22 14:58:00 Not Assigned
822 BOPP_2 operator report saying no power on panel and cant not power up doing reset found dust accumulate inside busbar found main braker on mcc room re set power up and ready for auto need to blow busbar dust out for better function 2026-03-02 13:44:41 Not Assigned
823 BOPP_2 shuttle not moving. found error code on CPU module. tried resetting. Thomas came in in the morning with his lap top and detected the bad input module. no follow up needed. an input and an output module are in locker behind Paul's office. in tight situations, can change out input modules till problem goes away 2025-04-07 10:59:03 Not Assigned
824 BOPP_2 inside shuttle not moving. found contactor was not engaging when inverter was activated. contactor was not mounted on rail. it was a very tight spot but got it to mount up and everything started working. retightened all the terminals 2025-04-07 11:04:57 Not Assigned
825 BOPP_1 P-3 crane not wanting to move once the crane put core in the core location. cleaned the sensor that tells the crane if the core is off the cradle. it was still not operating correctly so i rode the crane and seen where the senser was moved by a bracket it hit. fixed the bracket and moved it back 1/8 inch so it wouldn't hit again and adjusted sensor. Monday morning went back up and changed a washer to better give adjusting Clearence. no problems with crane so far. 2025-04-07 11:16:11 Not Assigned
826 BOPP_1 Called around 22:00 Crane shutting down over jrshuttle when unloading core on shuttle. After crane unloaded core on shuttle it would lose stop. I found that the limit for that position was not activated. So I adjusted limit up around 1/8 inch up and watched run about 4 missions all good. 2025-04-13 22:00:39 Not Assigned
827 BOPP_1 Called around 22:00 Crane shutting down over jrshuttle when unloading core on shuttle. After crane unloaded core on shuttle it would lose stop. I found that the limit for that position was not activated. So I adjusted limit up around 1/8 inch up and watched run about 4 missions all good. 2025-04-13 22:00:42 Not Assigned
828 BOPP_1 Call in 3:00 Crane stopping right over shuttle about mid way. Found that the host position was off about 1/2 inch to high. Check encoder coupling thinking it might be loss but was not and everything else looked good. Reset value check missions all good. 2025-04-13 22:08:49 Not Assigned
829 BOPP_1 Call at 6:00 crane would not go north or south up high but would go north and south in low position. Found that the host position was off again. This time it was about 1/2 too low. So I started to think encoder bad because when we replaced drive shaft we did hit bearing assemble over and that could have damaged encoder. Once I started removing encoder I noticed that the coupling was tight but after putting a wrench on it to loosen it the coupling moved a little. So I put everything back together and set value ran missions all good. Thanks Paul for the help. 2025-04-13 22:17:54 Not Assigned
830 BOPP_1 cpu keep going into reset CHAGE OUT CPU, CHANGE OUT POWER SUPPLY ,CHECK RELAY CUBES 2025-12-19 14:14:53 Not Assigned
833 BOPP_1 Rey operator call saying cutting arm string filament busted need to be replaced 05\13\2025 10;00 0m to 11;00 pm found the new string and got it replaced 2025-05-13 23:02:39 Not Assigned
834 BOPP_1 alfredo p 05\18\2025 operator call reporting brockend brush collector come off from busbar bopp1 4:30 to 5:30 AM found Brocken brush and replaced for the new one need replaced all the brushes 2025-12-19 14:14:13 Benjamin Leita
835 BOPP_1 call in: shuttle will not move remove chain so they can push shuttle. but could not because of damaged cable carrier. 2025-12-19 14:13:04 Not Assigned
836 BOPP_1 call in: crane slipping down with heavy load. adjusted brake. 2025-05-27 07:51:36 Not Assigned
838 BOPP_1 easy power supply went up in DC volts. adjusted volts. got crane off candelier. moved back to home and set to auto. then had to delete missions. also shut down stacker 3 for 24 volt power supply burnout followed up monday with stacker 3. no other follow up needed 2025-06-02 15:16:20 Not Assigned
839 BOPP_1 call in: packing crane 14 would not go up or down and packing crane 13 would not close. pk 14 1. check remote looks good. 2. went to top and check breakers and fuses and found one bad fuse. ( 3F01-03 south fuse was bad. after replacing fuse that did not fix the problem, so I got the print and found that the fuse was for clamps. started tapping on contacts and it started working. pk13: 1. found that the crossbeam sensor on the east arm was not aligned. I added a shim on one side of the sensor mounting bracket so the sensor beam can move a little to the south. 2. also found that the open clamp stop limit was missing a bolt, so I added a bolt. all good 2025-06-04 14:36:48 Not Assigned
840 BOPP_2 Call in. South east outrigger rubber rolled off wheel. Replace wheel. 2025-06-05 07:13:16 Not Assigned
841 BOPP_2 Call in. South east outrigger rubber rolled off wheel. Replace wheel. 2025-06-05 07:13:30 Not Assigned
842 BOPP_1 Call in. East cradle core sensor damaged and bolts for Teflon block broken Replace broken sensor and bolts Follow up. 1. Selicon wire. 2. Spare parts. Sensor and bolts. 2025-12-19 14:12:09 Not Assigned
843 BOPP_1 Call but did not come in. Operator said there is no light on c and y lazer encoder told him to leave down. Follow up 2025-12-19 14:10:52 Not Assigned
844 CFP Call but did not come in. Operator said Carriage was spinning fast in home position. Told him to leave down no cells Follow up 2025-12-19 13:23:55 Glenn Hasdorff
845 BOPP_2 ENCODER LOVE JOY BROKE. TOOK APART AND REPLACE LOVE JOY. NO FOLLOW UP 2025-06-09 13:41:43 Not Assigned
846 BOPP_1 TD 2 WOULD NOT COME ON. I DID ALL I COULD, HAD TO LEAVE DOWN TILL NEXT MORNING. PAUL AND I WORKED ON IT, THEN THOMAS CAME IN, AND STILL HAD TO LEAVE DOWN. MONDAY THOMAS AND GLEN FIGURED IT OUT STILL KEEPING AN EYE ON IT. ITS STILL WORKING 2025-06-09 13:45:05 Not Assigned
847 BOPP_1 END TABLE ON LINE 14 WOULD NOT EXCEPT ROLL. AFTER CHECKING AND FINDING NOTHING, BEN CALLED AND TOLD ME ABOUT A HIDDEN SENSOR WAY IN THE BACK. TIGHTENED SENSOR AND ROLLS STARTED AGAIN NO 2025-06-09 13:49:06 Not Assigned
848 BOPP_2 crane 2 would not run any global mission due to crane 3 showing offline and was dead had no power check on board panel, rebooted , bypass crane 3 so crane 2 could run manually and global could use arms manually 2026-03-02 13:43:21 Not Assigned
849 BOPP_1 20:30 call in: operator was putting a roll up in manual and as he was trying to go south in cantilever the crane would go north. After operator told me the plant lost power around 16:00 and the crane hasn't move sense then I rest onboard power, and the crane worked in both directions. 2025-06-23 07:54:15 Not Assigned
850 BOPP_2 Got a call around 2:35 that Crane 2 would not go up operator said it had chain slack and he could not get it to go even with button Got on crane 2 tried to hold chain slack button crane still would not go up called several people finally talked to Paul he gave me an idea but that was not the issue then called Glen and he talked me through . There were a couple of issues 1.Breaker for lights was tripped but needless to say that’s not the only thing that it controlled it also controlled the breaker for the ac in plc cabinet and communication module in the drive panel so when I turn the breaker in plc panel off the breaker in the drive panel stayed on issue 2. After that was stable checked the communications module for the a Z drive and it was not on so I changed the module out and was able to home out crane and watch crane run a couple of missions back to auto finished around 6:30 2025-06-29 08:08:32 Not Assigned
851 BOPP_2 Got a call around 2:35 that Crane 2 would not go up operator said it had chain slack and he could not get it to go even with button Got on crane 2 tried to hold chain slack button crane still would not go up called several people finally talked to Paul he gave me an idea but that was not the issue then called Glen and he talked me through . There were a couple of issues 1.Breaker for lights was tripped but needless to say that’s not the only thing that it controlled it also controlled the breaker for the ac in plc cabinet and communication module in the drive panel so when I turn the breaker in plc panel off the breaker in the drive panel stayed on issue 2. After that was stable checked the communications module for the a Z drive and it was not on so I changed the module out and was able to home out crane and watch crane run a couple of missions back to auto finished around 6:30 2025-12-19 13:22:16 Glenn Hasdorff
852 CFP operator bobby from CFP call saying the rotating arm on wrapper hit the cutting film arm and need it put back together because hi was short on operator don't know how make the other wrapper operate remove the Brocken arm and modify the blade arm on new position 07\02\2025 CFP WRAPPER i work from 11'00 to 3;00 am 2025-07-03 07:58:40 Not Assigned
853 BOPP_1 keyboard quit working. took the one out of Q1 in our shop but would still not work correctly. took the one out of line 2 and put in there because a roll was coming off and they would of had to shut down the line. once installed everything worked properly and now have to get it working for line 2 when it comes back up repair one to replace line two 2025-12-19 14:09:28 Joseph Prusick
854 BOPP_1 keyboard quit working. took the one out of Q1 in our shop but would still not work correctly. took the one out of line 2 and put in there because a roll was coming off and they would of had to shut down the line. once installed everything worked properly and now have to get it working for line 2 when it comes back up repair one to replace line two 2025-12-19 14:09:02 Joseph Prusick
855 BOPP_1 bopp1 stacker 3 tore up tranferdeck 3 back stop and fork sensor tack welded back stop and fork sensor bracket 2025-12-19 13:47:43 Not Assigned
856 BOPP_1 crane would not power up cpu keeps going into reset 2025-12-19 13:43:59 Not Assigned
857 BOPP_1 Call in no power to upper shuttle bopp-1 Found that main breaker was tripped. Check upper shuttle panel and current collector. it all looked good. Reset breaker. Watch shuttle run for 1 hour. all good. 2025-08-03 08:24:11 Benjamin Leita
858 BOPP_1 bay 4 would not transfer pallet onto shuttle took pallet down manly from bay 4, cleared missions , rebooted upper shuttle ,checked all Sensors on bay 4 and shuttle ,resent pallet back up pallet stopped on bay 4 put shuttle back in auto pallet would still not transfer to shuttle , let bay 4 and shuttle in auto shuttle was in the right position noticed hand shake sensors were pointing down on bay 4 table adjusted sensors the made signal and pallet took of and loaded on shuttle after pallet took off put bay 4 in manual and tighten up sensors put back in auto and watch run several missions thanks Doro V 2025-08-11 11:47:39 Not Assigned
859 BOPP_1 Upper shuttle sitting at home position not taking the mission waiting on Bay 4 There is likely old mission data stuck in the Upper Shuttle that cannot be cleared by the warehouse program. These steps will clear the old data and restart the shuttle. 1. Put upper shuttle in manual using the warehouse program (Upper Shuttle -> Manual) 2. Shutdown warehouse program (System -> Exit, enter PIN) 3. Restart warehouse program (Click BP1 WH Q1 icon on desktop) 4. Wait for warehouse program to completely startup 5. Clear Upper Shuttle mission (Upper Shuttle -> Function -> Abort Shuttle Mission) 6. Return Upper shuttle to auto (Upper Shuttle -> Reset -> Upper Shuttle -> Auto) This should clear any old mission data out of the Upper Shuttle and allow the Bay 4 mission to continue. If it does not automatically start, you may need to reassign the shuttle mission by clicking (UDC -> Reassign US) 2025-08-12 09:11:22 Not Assigned
860 BOPP_1 Transfer deck would not power up Walk up to stacker and immediately noticed that the radio was off and went straight for 24v and sure enough the fuse was blow, changed the fuse and power came up. After that tried to put transfer deck back to auto it would not go to manual or auto so i restarted the program and then I was able to go to manual then auto. Watched several missions after that called it good 2025-08-14 07:59:29 Not Assigned
861 CFP film kept breaking check sensors change film adjusted air pressure dancer arm weld broke so took off needs welding 2025-12-22 14:39:10 Glenn Hasdorff
862 BOPP_1 got call from rosa pallet entry operator from bopp1 she describe that the previews operator dot leave a note of the situation she cant not send up 48s only 96s pallets if she send 48s pallets the system report is a 96 i check all the sensors and was good all of them 2025-12-19 13:43:45 Not Assigned
863 BOPP_1 operator from pallet island report saying that having problems with the wrapper sense friday bopp1 from 6:00 to 8:00 i re set a inverter that has alarm on it try on auto works good it wrap 7 pallets after that the machine go in to alarm with no codes on screen 2025-12-19 13:43:25 Not Assigned
864 BOPP_1 Upper shuttle won't pick up a pallet from TD 2 1. Switch upper shuttle to Manu 2. in function mode, clear mission inside shuttle 3. push shuttle to Auto 2025-09-03 09:28:27 Not Assigned
866 BOPP_1 pallet wouldnt transfer to upper shuttle , pallet wouldnt transfer to upper shuttle ,so i put upper shuttle in manual , exited the system logged back in and aborted missions on shuuttle and transfer deck , put in auto and ran good 2025-09-08 09:14:39 Eric licerio
867 BOPP_1 p3 wpuld not put roll on to scale everything lookede good so i turned all power off and rebooted and it ran good all night 2025-09-08 09:15:51 Eric licerio
868 BOPP_1 line 16 elevator cover got in a bind and wouldnt go up pressed contact in and it eventually came up and ran good the rest the night 2025-12-22 14:02:27 Eric licerio
869 BOPP_1 test test 2025-11-24 14:23:06 Chara Leita
870 CFP GOT CALLED AROUND 13:30 Sunday ON ENTRY TABLE WOULD NOT GO FOWARD BAD CONTACT. When i got here Chano was here found bad contact and changed it out. 2025-12-22 14:57:18 Not Assigned
871 BOPP_1 got call around 1730 that the jr shuttle was losing power got here around 1900 Shuttle lose power around forklift crossing area so i looked at the bush sensors and relays. found two relays out reseated them and got power back. after that encoder keep jumping found two spots that the track was damaged repaired all good. Carl did mention that TD2 will not power up, so I went to look at it and seen that one of the modules had a U< alarm. so, after resetting it and the alarm would not clean I left it down. 2025-12-19 13:42:48 Benjamin Leita
872 BOPP_1 WRAPPER FILM KEEPS BREAKING MADE ADJUSTMENTS IN WRAPPER PROGRAM. 2025-09-17 13:20:19 Benjamin Leita
873 BOPP_1 Got called that stacker 2 was in high position in transfer deck and could not recover When I got here looked for y position wire number 429 and jumped it with 24v+ wire number 3 so I could move the stacker out of transfer deck ounce out lowered stacker platform reset then back to auto stacker came into transfer deck but did not drop pallet off so took off manually clear missions then back to auto it ran for awhile I had already left and got called that it was at the lower position limit now so checked wires and when i would tug on wire module would reset so took wires number 428 re-stripped them put back and tighten terminal block it was stable watched missions looked good 2025-12-19 13:42:27 Not Assigned
874 BOPP_2 Cutting arm was not cutting Trouble shoot found the wire was not getting hot so checked panel to maker sure no fuses blown then went to check wire make sure not broken as I was checking wire saw that the ring lugs from the cutting arm wire were loose so I repositioned them and tightened them up I watched several pallets looked good 2025-10-06 07:02:53 Not Assigned
875 BOPP_2 Jumbo roll shuttle was stopping short to all positions for roll pick up While I was on a call from bopp1 Rudy stopped me and said J/R shuttle was stopping short went to look and shuttle did fine so I left this was in the morning around 10:00 2025-10-06 07:11:38 Not Assigned
876 BOPP_2 J/R shuttle stopping short Came back for J/R shuttle this time talked with Thomas and he changed some settings temporarily and it did good so I left 2025-10-06 07:14:22 Not Assigned
877 BOPP_2 J/R shuttle stopping short Got called back because it was doing it again when I got here I was texting with Thomas and the settings that were entered were temporary so when they reset power they went back to original settings Thomas did some other changes to settings to make work and permanent for the night I stayed and watched several missions this time and it looked stable so I left did not get a call for the rest of the night for J/R shuttle 2026-03-02 13:42:47 Not Assigned
878 BOPP_1 Monitor on line 4 for panel turning off. Came in Saturday to work on line 12 project before I got here Alex had called for line 4 monitor turning off so I went to check and sure enough it was off so I moved the plug for monitor and it stayed on, 15 min later Alex called back said it did it again so went back and this time tightened the terminals for plug in back of monitor seemed to work, I did not get call back on it until Monday morning at 5 so I came in moved wires behind easy chassis and it came on watched them roll out and seemed stable for now next roll out is at 8AM. 2025-12-19 13:41:38 Not Assigned
879 BOPP_1 operator JAVIER call to report that line #14 shuttle don't able to operate eater manual or automaticn # 1 found backer trip #QM35 2 inside the panel # 2 found pipe has drop on top of sensor # 3 east top push by stock of wood embors re set panel after and get it back on auto need to build guards around to protect sensors and the equipment 2025-12-19 13:39:26 Not Assigned
880 BOPP_1 BOPP-1 WILL NOT RUN IN AUTO To All, I got a call a little after midnight about the line 4 crane not able to power up.  There was no green light on the EASY CPU and checking the 1.x inputs revealed the cause was a thermal fault (breaker tripped) because input 1.4 was not on. There were no tripped breakers in the panel.  Relay 0KA03 operates a contact that turns this input on.  I added 2 jumpers to bypass the relay so the operators could get the full rolls moved while we figured out the cause - line 4 was already down at this time with 2 rolls on the winders. We found the auxiliary contact on breaker 1QM1 (high speed hoist motor) was bad.  While trying to remove the aux contact the breaker's plastic shell fell of exposing the inside of the breaker.  At this time, we left the relay bypassed and went to BOPP2 to try to find a replacement breaker. The original breaker was set to 25A which is reasonable for the 13kw motor.  The closest we could find was either 16A or 32A.  We installed the 32A breaker and its auxiliary contact, removed the bypasses around 0KA03, and tested the crane.  Everything worked as normal. -Thomas 2025-10-23 10:09:25 Benjamin Leita
881 CFP stacker would not go into auto would move manually up and down and forks go east and west. did it fixed? 2026-03-02 13:41:48 Not Assigned
882 CFP table after wrap machine would not go forward broken drive chain and motor had no adjustment tension 2025-12-22 14:57:03 Not Assigned
883 BOPP_1 operator core call saying cannot not move p-3 on manual. found busted cable on center position for the flag caused by missing guide on x travel an the braked that hold all the censors kick a few flags on the north side on warehouse because also the wheel flinch is bad make the crane shift to the west and damage the sensors hinting the flags i call paul lopez and joe villareal for help to found parts to restore the issue from 3;00pm to 11;30 pm 2025-12-19 13:25:30 Alfredo Pinon
884 BOPP_1 operator call saying upper shuttle don't take pallets from by #4 check and try some pallets and don't got any assignment from the program it self i has to call yiduo for support and got it going on on full operation Saturday 11-29-2025 at 1;25 am to 3;45 am 2025-11-29 03:42:26 Not Assigned
885 BOPP_1 packing crane 12 would not move north and south. the contactor the functions the north and south popped. main cause is that the packers slam it into the packing crane next to it or the c-hook. reset the contactor and made sure it worked. no follow up needed 2025-12-04 14:05:36 Not Assigned
886 BOPP_2 host chain is at 2% stretch both sides replaced both sides 12/03/2025. sprockets need to be replaced also. 2025-12-08 13:45:01 Not Assigned
887 BOPP_1 shuttle lost power trip main breaker no power ,check check brushes fusses, found trip breaker restset had mission problem got back in auto 2025-12-16 08:11:18 Not Assigned
888 BOPP_1 power keep kicking off would not stay powered up check out issue ,cpu keep going into a reset, unplugged power supply, plugged back in ,i tapped accidentally hit green on/cnc/vok cable on power supply and lost power, replunged cable everything stayed power up 2025-12-19 13:21:41 Glenn Hasdorff
893 CFP Call-in: broken pallet missing flat got stuck on chain table check out problem, table had no power, found trip breaker, tripped, pallet would not move missing board was stuck on frame of table, had to take 6 pallets of manfully including tall pallet because wound not go through system missing that board got everything back in auto 2025-12-22 14:56:23 Doro Villegas
896 BOPP_1 Call-in: shuttle misplacement on encoder at line 4 Found bad spots on encoder track. Fix with hammer. 2025-12-23 13:15:31 Benjamin Leita
899 BOPP_2 Entry pallet not going forward, errors on PC12 When an entry pallet not being assigned UDC, it is most likely due to no slave pallet length given from Wrapper PLC. This may caused by communication interrupt between PC and PLC. To recover the communication error, click "Entry" button, then hit "Reset button". This will fix the problem. 2026-01-02 08:16:36 Yiduo Wang
900 BOPP_1 Call-in: would not go down Came in found that packing crane was working but I changed the remote anyway just in case it was the remote. asked him why didn't they use packing 14 and he said that it does not go down I said ok and left. 2026-01-08 09:49:00 Joe Moya
903 BOPP_2 material control requested open second level for resin and end board due to cell shortage program modified so that both level one and level two are used for resin and end board. your can see the status in ash cell summary 2026-01-19 08:04:21 Yiduo Wang
904 BOPP_1 C hook would jitter when going west. we took apart the controls on the crane and found a 24V DC wire slipped out of a normally open contact. 2026-03-09 13:22:37 Manuel Tovar
905 BOPP_1 Call-in: called in Friday (1-23-26) stacker 3 would not unload pallet check all sensor pallet present se4nsor was loose realigned and tightened tested put back in auto 2026-01-26 07:45:40 Doro Villegas
906 CFP called in (1-23-26) table would not move check out breaker & sensor could hear motor kick in but would not move, climb under table seen chain broke. Had to remove covers chain got jammed between sprockets reran chain put new master link put covers back on tested put back in auto issue from broken wood between chain 2026-01-26 07:50:22 Doro Villegas
907 CFP Call-in: tower not in home position i rebooted the program moved the tower to home position and put back in auto and it ran 2026-03-09 14:15:24 Eric Licerio
908 CFP Call-in: stacker 4 lost power i checked all e-stops checked brushes and busbar and power supply everything was good so checked the main breaker box and found a tripped breaker to the busbar after that it powered up and went back in auto 2026-01-27 14:29:30 Eric Licerio
909 BOPP_2 Encoder positioning was jumping around. showing 300,000 in two different locations. When carne was over the jr shuttle value should be 300,000 and the number was right +- few. Once crane moved north (number was decreasing) and was over the second buffer (not sure buffer number) the number would jump back to 300,000 and start decreasing again. The crane would run over to the winder and stop over the winder with a wrong value. You can put the crane in manual and drive it to the second buffer, and it will stop there because it was at the 300,000 value. You can put the crane in manual override and drive the crane back over the jr shuttle and the value would go back to 300,000 +- few. How we fixed it. In the PLC panel we recede all the plc cards and once we did that the value was correct. We did all the normal checks first and receding the cards worked. follow up: we need a good working x-encoder. 2026-03-05 14:17:39 Joe Villarreal
910 BOPP_2 line 15 would go into alarm every time we tried to switch to auto Service Summary – Inverter Fault F033 The elevator was repeatedly throwing Fault F033, which corresponds to Auto Restart Tries Exceeded. Initial diagnostics included ohming out the fuses and motor, all of which tested good. Based on the fault behavior, we proceeded to replace the inverter. After replacement, the elevator powered up, but the chains would not engage. Chano transported both inverters to CFP for bench testing on the test station. The test station confirmed the issue was related to parameter settings. After retrieving and loading the correct parameters, the inverter operated properly and the elevator resumed normal function. 2026-01-30 08:08:52 Eric Licerio
911 BOPP_2 line 15 would go into alarm every time we tried to switch to auto Service Summary – Inverter Fault F033 The elevator was repeatedly throwing Fault F033, which corresponds to Auto Restart Tries Exceeded. Initial diagnostics included ohming out the fuses and motor, all of which tested good. Based on the fault behavior, we proceeded to replace the inverter. After replacement, the elevator powered up, but the chains would not engage. Chano transported both inverters to CFP for bench testing on the test station. The test station confirmed the issue was related to parameter settings. After retrieving and loading the correct parameters, the inverter operated properly and the elevator resumed normal function. 2026-01-30 08:08:56 Eric Licerio
912 BOPP_2 stacker 1 hit water line and got stacker 1&2 wet proper steps when warehouse stackers get wet stacker 1.moved stackers out of water then shut down 480 disconnect and locked out 2.shut down water in back of warehouse then drain water line 3.open doors on panel wipe down and water set up fan to blow in panel and dry 4.got rags and leaf blower clean and dry bus bar 5.wipe down Lazers reflectors and sensors on stacker 6.open trenches vacuumed water that went in trench 7.got with safety to make sure waterline that got hit was fixed before starting stacker 8.unlocked disconnects power up stackers 9.check all functions up down cross travel fork east and west 10. moved stacker to home position greased bearing and lube gear because don't want damage gear or bearings in 3 months due to water 11.test a mission in auto 2026-01-30 11:11:02 Doro Villegas
913 BOPP_1 Call-in: shuttle was not getting the missions are moving once the pallet was on, but would move manually. reset shuttle, cleared missions, and still would not take mission. had them stack pallets till Thomas came in and looked at his computer After Thomas came in, we looked at the program, checked the power source coming in. sometimes power was good, sometimes power was only 58 volts on one of the legs. checked brushes all was good. while checking buss bar again, figured that the buss bar did not have enough pressure on the current collectors to make a good contact, so we moved the bracket up a smigget, to put pressure on it and it worked. 2026-02-02 09:08:55 Joseph Prusick
914 BOPP_1 crane 1 in building 2 had encoder issues. crane would not move. they said it had to be changed by computer. called Paul and he said there is a manual override that they can use till others get there in the morning to help out Joe Joe and alfredo took the encoder off and reset the value with the pt-100 2026-02-02 09:12:59 Joseph Prusick
915 BOPP_1 1/29/2026 P3 dropped core on shuttle. cradle sensors (core presence) not working. damaged: 1. idle and drive wheel assembly 2. bus bar brackets 3. west side brush bracket 4. j-box for relay west side follow up: 1. rebuild idle and drive wheel assembly 2. fix cradle sensors. 2026-03-02 13:39:06 Joe Villarreal
916 BOPP_1 “The shutdowns are of two types, some are at the transition from steady speed to deceleration when nearing the target, others are seemingly random during steady speed movement.” That turned out to be more true than we realized. There were two completely different causes of the frequent shutdowns, one coming from Easy and the other from Bosch. On Friday afternoon we isolated the encoder as the cause of the random shutdowns, we could make Easy decide to shut down the shuttle anywhere by tapping on the encoder. Its suceptability to vibration explained why we could get by running at a very low speed but have many shutdowns when running faster. However, after replacing the encoder in the late afternoon the other type of shutdown continued, always during deceleration when nearing the destination. We observed the Bosch supply module VM60/EB-TA was turning off its BTB2 light at the time of the shutdowns during deceleration, indicating it was making the decision to shut down. There are four different possible causes of BTB2 shutting off, and using the diagnostic card isolated the specific fault as “BF” or ‘ballast fault’. This machine uses a Bosch EBM-1000T “External Ballast Module”, actually a dynamic braking resistor, to absorb the energy generated by the motor during deceleration. So the BF fault means either the VM60/EB-TA isn’t sending the deceleration energy to the EBM-1000T resistor for dynamic braking or the resistor isn’t able to absorb it. That also was speed related, when traveling slow there is less inerial energy to absorb at deceleration but at a higher speed it could not absorb the additional intertial energy and would shut down with the BF fault. We next observed the EBM-1000T has two fans at the bottom of the module to reject the heat from the resistor and only one fan was running which would make the EBM-1000T tend to overheat during deceleration. However, replacing the fans did not change the BF faults. Next step was to replace the VM60/EB-TA Bosch supply module itself and that completely eliminated the shutdowns during deceleration. Carl related that what he saw late on the Tuesday night shift, early Wednesday morning, was also a combination of shutdowns, some shortly before the destination and others at random locations while traveling at speed. Knowing that the bad encoder we found this afternoon was not there on Tuesday night (it was installed on Wednesday), we are left with the assumption that the two original problems were: 1. Bosch VM60/EB-TA module causing EB faults during deceleration (found and replaced Friday evening) 2. Damaged encoder cable in panel door causing Easy motion faults (found and replaced Wednesday afternoon but a replacement encoder introduced at that time made it worse) As would be expected from this type of event where many parts were changed, we will have a fairly long list of followup items to take care of. But that can wait until Monday. Again, thanks to everyone for all their support thorugh this long troubleshooting. 2026-02-06 08:06:09 Yiduo Wang
917 BOPP_1 network connections RDS 14 to connect the plant Reel Data System (RDS) to the Goebel 14 PLC requires an ethernet path from the handling network (172.22.n.n/18) to the slitter machine network (10.119.113.n/24). For starting up the line we made a temporary direct connection between the two networks but that is not desirable. To keep the two respective networks separate and secure from each other we are installing a Siemens Scalence S615 NAT module as a bridge between them. The S615 uses NETMAP to only allow traffic from specific IP addresses to pass between the two networks and also to translate or map the IP addresses between the two networks as the packets are passed through. This requires a small range of IP addresses in the Goebel machine network to be reserved for use by the S615 module. Based on researching the IP addresses presently in use in the Goebel 14 machine network using two programs, Siemens Step 7 Portal and Colasoft IP scanner, I am requesting to reserve the presently unused address range 10.119.113.240 to 10.119.113.249 for use by the Scalence S615 module. The S615 module itself will be 10.119.113.240 and will be able to be pinged at that address, while 241-249 are used for address mapping as shown below. Handling PLC network Goebel XS 14 machine network vlan1 (INT) vlan2 (EXT) 172.22.12.149 S615 NAT router mgmt S615 NAT router mgmt 10.119.113.240 S615 Netmap 172.22.12.142 (mapped address) < bidirectional > PLC 10.119.113.2 172.22.12.101 PC30A RDS < bidirectional > (mapped address) 10.119.113.241 172.22.12.102 PC30B RDS < bidirectional > (mapped address) 10.119.113.242 172.22.19.203 Step7 Portal prog < bidirectional > (mapped address) 10.119.113.243 172.22.19.204 Yiduo develop < bidirectional > (mapped address) 10.119.113.244 172.22.10.200 Intermapper < bidirectional > (mapped address) 10.119.113.245 available not config (reserved address) 10.119.113.246 available not config (reserved address) 10.119.113.247 available not config (reserved address) 10.119.113.248 available not config (reserved address) 10.119.113.249 You are welcome to share this information with Reiner as it may be helpful for him to know how these addresses are intended to be used. If there is a need to move to a different IP address range we can do that. Presently we are configuring the S615 module in the office and then will be installing equipment in the new network cabinet for some days before the new connection goes live. I will let you know when we are ready to switch over from the temporary direct connection to the new connection through the S615 module. As a side benefit if desired, the PLC will be able to get NTP time reference from the S615 module at 10.119.113.240. I don’t know if this PLC already has a way to set its internal time of day clock, but if not this would help its fault log be more useful. We’re planning to do this in the Bonfanti panel with its S615 module and S7-1500 PLC also. In the future we will be going through this same process with Goebel 13 and Goebel 12. 2026-02-06 08:11:16 Yiduo Wang
918 BOPP_1 P3 crane/shuttle conflict during certain mission combinations involving south side of warehouse Two times this afternoon between 5 and 6 pm the P3 warehouse crane and JR shuttle almost collided but the safety interlocks stopped both machines in time. No damage was done but the recovery was awkward. The second time it happened we were able to confirm that this specific combination of slitting roll missions creates the problem: 1. First slitting roll mission is for a roll from the north half of warehouse and the shuttle does not have an empty core for the crane to pick up 2. Second slitting roll mission is for a roll from the south half of the warehouse Here is what happens: 1. P3 crane loads first slitting roll onto the shuttle from the north side 2. There is no core to pick up so the shuttle parks on the north side (parking is on the side it came from) 3. When the crane has parked the shuttle is free to leave the warehouse. When the crane has parked the crane is also free to receive its next slitting mission. Both happen at the same time. The shuttle starts leaving the warehouse and the crane starts moving south to get its next roll, so the crane is moving right toward the departing shuttle. 4. Then the safety interlock system functions—crane stops because shuttle is not clear and shuttle stops because crane is in the shuttle area. At that point neither machine can be driven because each knows the other machine is in the way. The first time it happened I had to use a bypass switch in the P3 ground panel to allow the shuttle to leave, and then had to reboot the crane to get it out of the faulted condition. (And the CPU decided to go into Reset right then but that is another story.) The second time I was anticipating it and put the crane in manual as soon as it started moving south toward the shuttle. That stopped the crane in time before the interlock shut everything down. Manually drove the crane back to the parking position and erased the crane mission (“Z”) and that released the shuttle to continue leaving in automatic. Jason had to reenter that slitting roll for them to order it again. 2026-02-06 08:40:40 Yiduo Wang
919 BOPP_1 ADAM-6052 First, the 3 modules called STK1, 2, and 3 were configured in basic mode because they only received from the ones labeled TD1, 2, and 3. When the Exit modules were added, the TD modules were changed to advanced mode and STK were not. This caused the Exit to set a TD output and STK to reset it periodically. After disabling the STK module's channels the problem partly went away. There were still a few blinking outputs... The solution ultimately was to disable ALL of the unused channels in all of the modules. Apparently, even channels mapped to 255.255.255.255 would somehow reset outputs that were set by another module. After changing all of the period times to "0" on the unused channels, the problem completely disappeared. 2026-02-06 08:43:07 Yiduo Wang
920 BOPP_1 to clear the “Discharge. Battery” error message on the Line 4 crane using the information in this guide. The P2 ground panel still has the error message and needs the same fix. Quite a few years ago you replaced the D size lithium batteries in all the Easy power supplies as you rebuilt each one and that project was very successful. Now those batteries have reached end of life and we need to plan an organized replacement again. We have 20 Easy cabinets in service (including the old Q1 and the test panel) and each of them has one Easy power supply. Besides that you also have a stock of spare Easy power supplies which is necessary. We will need to order enough batteries to do all of them and then mark the date on each one as we replace it. Last time you used both silicone caulk and tyraps to hold the large D cell in place and that seemed to work good on the moving machines. If I remember correctly you found that without the silicone the vibration on the moving machines broke the battery terminals. 2026-02-06 08:47:25 Yiduo Wang
921 BOPP_1 P2 crane hoist overload protection test performed on 1-17-03. Ratings: Jumbo roll working load is maximum weight of 6 metric tons or 13228 pounds. Crane rated load capacity is 7 metric tons or 15432 pounds. Hoist servo modules have 150 amp peak current rating. Hoist servo optimization module DIP switch was already set to 70% current value limit. Changed R25 on optimization module to 16.2K ohms and connected 24 volts to Mred input for 50% current setpoint limitation. 150 amps x 70% x 50% = 52.5 amps current limit Test #1--rated load operation Test load is 16235 pounds (105% of rated load) Runs up and down at low and high speed with no problems. Current while hoisting high speed is 30 to 35 amps, with a maximum of 43 amps. Test #2--overload with current limit protection Test load is 23660 pounds (153% of rated load) Runs up and down low speed with no problem. Current while hoisting low speed is 34 amps. When high speed hoisting is attempted, servo module limits current at 49 amps which reduces speed. EASY control shuts down with 'trajectory error' due to the limited current/torque/speed. No damage to rotating beam. Conclusion: The current limit feature now functions reliably to limit the motor current to approximately 50 amps, and at 50 amps there is no structural damage to the crane. After seeing the effectiveness of the current limit feature in the Bosch servo module, there doesn't appear to be a need to install the "bent beam" sensor arrangement that we had planned. Total materials cost for adding the current limit feature: $1.27 2026-02-06 10:55:07 Yiduo Wang
922 BOPP_1 Call-in: stacker 3 pallet crash, pallet was caught on gears and the forks left without the pallet completely. Feb 4th 2026 9:30pm jack up pallet as best as possible. get forks under pallet, then wrap yellow straps on pallet to stacker 2 TD, pull pallet with stacker 2 while moving stacker 3 forks in simultaneously. 2026-02-10 14:31:10 Manuel Tovar
923 BOPP_1 Call-in: called in at 7:15 friday 2/6/2026 sensor loose, not allowing pallets to be sent up. adjusted the sensor and removed an obstruction that was in the way. entry operator couldn't adjust entry sensor, called me in to fix it. mission issues happened after start up, deleted a mission brought pallet down and put upper shuttle in auto. 2026-03-09 13:22:50 Manuel Tovar
924 BOPP_1 Call-in: conveyor not moving, called in at 10pm 2/7/26 conveyor would not move because E-stop was pushed in. fixed it as soon as i got here. Then I received a complaint about elevator conveyor stopping after 1 cradle. So i stayed and watched the machine run, a sensor was lower then it should have been. adjusted it and it was good to go. 2026-03-09 13:22:18 Manuel Tovar
925 BOPP_1 Call-in: 2/7/26 called in for core falling off slitting machine on line 12. operator did not see the core falling off the machine so it landed on the floor. fixed it by getting 2 come along's and 2 long yellow straps provided by slitting mechanic, i then proceeded to climb up p2 so if needed i could bypass the sensor 2026-02-10 15:25:46 Manuel Tovar
926 BOPP_1 Call-in: 2/9/26 call in after 1am called in for handshake issues with upper shuttle not responding and pallet crash on td3 came in looked at upper shuttle sensors were all good, then went back to pallet island computer, reset program, deleted mission, and hit auto, it started taking pallets just fine. after i checked on TD3 for a pallet crash, i manipulated the pallet onto the forks and i managed to run an exit in semi-auto. 2026-02-10 15:31:12 Manuel Tovar
927 BOPP_2 Call-in: inverter f 12 REPLACE INVERTER DID NOT WORK. REPLACE CONVEYOR MOTOR. BACK IN AUTO. 2026-02-13 10:53:19 Benjamin Leita
928 BOPP_2 Call-in: CALL IN CRANE-1 DYNAMIC BRAKE FAULT REPLACE BLOWN FUSE AND DIODE PACK. DID NOT WORK. REPLACE DYNAMIC BRAKE UNIT. WORKED, PUT BACK IN AUTO. 2026-02-17 11:26:13 Benjamin Leita
929 BOPP_1 Call-in: CALL IN LINE 12 REEL HANDING WOULD LOAD CRADLES TO SHUTTLE. REBOOT SYS. WORKS FINE AFTER REBOOT 2026-02-17 11:32:58 Benjamin Leita
930 BOPP_2 Call-in: shuttle was giving positioning problems. operator said that the shuttle would not home out after pushing home button. I knew that we have been having issues with positioning most of the week. first thing I did was. day one: 1. Check encoder arm. noticed brass bushing was worn out causing teflon block to ride at an angle also found that the belt was stretched and had damaged teeth. Found new belt but did not find brass bushing. After installing the arm back, I tried to home out the shuttle. And at this point the shuttle did not respond. I was able to drive the shuttle in manual but just could not home it. 2. Started to look into why shuttle would not home out. After resting the shuttle couple times and moving back and forward making sure all functions were working. I would try to home the shuttle thinking maybe if it was in a different location, it will work but it didn't but what did happen a couple times was after pushing the home button the shuttle drove east at a high speed and hit the bumper. 3. Next thing was to check inputs for home button. took remote apart to make sure remote was working and looks good but I was not seeing the input from the home button. Also, after checking to see if the east over limit was working, I manually activated the limit and got the red light on stack but could not reset it with remote. At this point I had been working on it for couple hours and cfp was down also so left it down. day two: After tracing down issue and removing ice cube relays to make sure they are good and making some adjustments to the east over limit arm the shuttle homed out. crazy not 100% sure why but we think it might be one of the relays. for sure thing is new belt (could be positioning issues all week) and adjust east over limit. follow up: parts for encoder arm 2026-03-02 13:38:15 Joe Villarreal
931 BOPP_2 Call-in: crane was losing power when traveling and after a couple resets it finally shut down no power and also no power to panel view. crane was over line 16 1. checked incoming power at j-box and it was missing one leg. 2. started to walk the bus bar down to look for separation. found it. 3. went to north side of bus bar and got a 2x4 and hit buss back together. you have to carful to make sure points go back together right. 4. power up all good 5. from the photos you can see what area it was at. follow up: 1. install physical stopper on north side to help keep the buss from moving north. 2026-02-23 08:03:28 Joe Villarreal
933 BOPP_1 North shuttle sliding plate out of alignment. This will work on all lines. Sliding plate was out of alignment. this should work on all lines 1. found tripped breaker (don't remember if it was east or west side) reset the breaker. 2. located contact for east motor. (you can see on the file that's attached) we wanted to move the east side of the shuttle. 3. found contact for east motor to slide plate north. (KM232.4) push contact in so east motor can move north. (make sure you just bump contact in to make sure you are going the right way) 4. aligned plate. 5. after plate is aligned test in manual to make sure all is good. Also, before you open the doors there is a step by step. 1. turn key switch on door and hold during while opening the doors. (do not let it go) 2. once doors are open you can pull out the safety door limits to bypass them. 3. then you can release the key switch. 4. power should stay on. 5. repeat steps when you are ready to close doors. (push door limits back in) 2026-03-04 16:25:45 Joe Villarreal
934 BOPP_1 wire on cutting arm busted Service Summary – Cutting Arm Wire Repair Found the wire on the cutting arm busted. Removed the damaged wire and installed a new replacement. Tested operation after replacement and no issues were observed. Machine returned to normal function. 2026-03-09 14:16:23 Eric Licerio
935 BOPP_1 safety barrier alarm was preventing the shuttle from functioning in auto Service Summary – Bumper Safety Barrier Alarm Issue Machine was triggering a bumper safety barrier alarm on every mission, preventing operation in auto mode. Initial inspection suggested a possible short in the bumper barrier wire, though no visible breaks or damage were found. Added slack to the wire connected to the bumper barrier to relieve tension and potential internal strain. Cleaned and wiped down the safety barrier sensors to ensure proper detection. After these adjustments, the machine was able to run missions in auto mode. Noted that the bumper appears slightly damaged, so a follow‑up inspection is recommended to prevent recurring faults 2026-03-09 14:21:56 Eric Licerio
937 BOPP_2 PALLET CRASH , DAMGAED SENSOR Service Summary – Optional Pathway Sensor Damage A pallet crash caused damage to the optional pathway sensor. Inspected the pallet and found it twisted from the impact. Straightened the pallet enough to safely remove it. Manually removed the damaged pallet from the area. Installed a new optional pathway sensor to replace the damaged one. After replacement, the system was able to return to auto mode with no further issues observed. ISSUE RESOLVED 2026-03-09 14:15:32 Eric Licerio
942 BOPP_1 TD 2 and 3 will not send off 2nd pallet after receiving. TD 2 and 3 will not send off 2nd pallet after receiving, both elevators will stay down after stacker takes the 1st pallet. during troubleshooting joe discovered input 7_3 wire number 12, was flickering, ben tested the input voltage and found the input voltage was only 3V's and not 10V's as it should be. we replaced the forks present sensor on both TD's and they started operating normally. 2026-03-20 09:11:53 Manuel Tovar
943 BOPP_1 Call-in: forks not centered on stacker 1, upper shuttle not moving reset program and stacker, and td, and checked ends of fork. got it to work. upper shuttle not moving, panel and all the lights were working, shuttle finally took pallet, bell going off like it was moving, but didnt move. i knew at that time to check the buss bar, and one leg was off. fixed 2026-03-25 13:36:35 Joseph Prusick
944 BOPP_1 Call-in: stacker 1 not working reset stacker, and program, it started working again and had to pull for trucks in the morning. next morning we went out to check it and found that the tension rod that held the tensioner in the forks was bent, and a sensor that was just replaced was loose. Alfredo heated rod and we straightened it out and fixed sensor and been running since 2026-03-25 13:47:19 Joseph Prusick
945 BOPP_1 P-3 dropped a roll on the shuttle was called at 2am and was told P-3 dropped a roll on the shuttle and it was bad. I called in back up and found that we were able to fix it without a crane. moved roll, fixed JR shuttle, and welded cracks that we found. Put it all back together and watched it do a couple of runs. Going to replace the old with new style sensors and put spy cameras up. 2026-03-25 13:56:30 Joseph Prusick
946 BOPP_1 Call-in: C-Hook quit going north and south workers slammed C-Hook into another crane. came in and reset the inverter. Chuck said he couldn't get the other crane over there because the C-Hook was in the way 2026-03-26 03:41:06 Joseph Prusick
947 BOPP_1 not working study 2026-03-26 12:24:15 Yiduo Wang
948 BOPP_1 not working study 2026-03-26 12:25:04 Yiduo Wang
949 BOPP_2 pallet crash a stack of 48" pallets hit the blue steel and twisted, causing the stack to fall. picked up pallets, one sensor broke. replacing sensor. 2026-03-27 08:22:00 Joseph Prusick